Page
4
Line End
3-Pole
MCP
I
3.438
1.719
(43.66)
3.281
I
I
2.292
(58.22)
I
Load End
Fig. 2-3 MCP Escutcheon Cutout Dimensions
for 3-pole
MCP
3. REPLACEMENT
OF
EXISTING MOTOR CIRCUIT
PROTECTORS
Panel Escutcheon Cutout Sizes
Existing cutouts must be modified to agree with
requirements shown in Fig.
2-3.
Existing handle mechanisms may need to be
modified or replaced. Consult Allen-Bradley for
additional information.
Only Q-Frame accessories may be
used.
Motor operators must be replaced.
Key interlock mounting brackets must be
replaced.
Consult Allen-Bradley for replacement styles.
Terminals must be replaced, see Table
2-1
for
replacement types.
Unless noted above, all other physical character-
istics are the same.
Handle Throw Positions
Internal Accessories
External Accessories
Terminal Wire Connectors
Other
WARNING
CONTACT WITH ENERGIZED EQUIPMENT CAN
RESULT IN DEATH, SEVERE PERSONAL INJURY,
OR
SUBSTANTIAL PROPERTY DAMAGE.
DO
NOT
ATTEMPT TO INSTALL
OR
PERFORM
MAINTENANCE ON EQUIPMENT WHILE IT
IS
ENERGIZED. ALWAYS VERIFY THAT NO VOLTAGE
IS
PRESENT BEFORE PROCEEDING WITH THE TASK,
AND ALWAYS FOLLOW GENERALLY ACCEPTED
SAFETY PROCEDURES.
Note: When replacing an existing MCP or circuit
breaker
of
the types listed above, make sure the volt-
age, continuous current, and interrupting rating
of
the new MCP are suitable.
40752-081(1)
Effective 2/03