Rockwell Automation Publication 442G-UM002A-EN-P - December 2016
45
Status and Troubleshooting
Chapter 4
Clearing Faults
Clearing faults in the access box requires cycling one of the fault reset signals
(GeneralFaultUnlatch or LockSequenceFault Unlatch) as specified in
.
The reset requires a leading and trailing edge of the reset signal within a specific
time frame. The pulse width must be between 10 ms…10 s. If the pulse width is
too short or too long, the reset function is not executed.
Figure 20 - Fault Reset Timing
Multiple Faults
It is highly unlikely that more than one fault will occur at the same time. If a
new fault does occur before a previous fault has been cleared, a new value will
be written to FaultCode deleting the previous one. The DiagnosticActive bit is
set with each fault, but will not change state if the second fault occurs before
the first fault is cleared.
1
0
10 ms to
10 s
Содержание Allen-Bradley Guardmaster 442G-MABE1
Страница 6: ...6 Rockwell Automation Publication 442G UM002A EN P December 2016 Preface Notes...
Страница 18: ...18 Rockwell Automation Publication 442G UM002A EN P December 2016 Chapter 1 General Description Notes...
Страница 22: ...22 Rockwell Automation Publication 442G UM002A EN P December 2016 Chapter 2 Safety Concept Notes...
Страница 46: ...46 Rockwell Automation Publication 442G UM002A EN P December 2016 Chapter 4 Status and Troubleshooting Notes...
Страница 48: ...48 Rockwell Automation Publication 442G UM002A EN P December 2016 Appendix A Specifications Notes...
Страница 54: ...54 Rockwell Automation Publication 442G UM002A EN P December 2016 Appendix B EtherNet IP I O Assemblies Notes...
Страница 59: ...Rockwell Automation Publication 442G UM002A EN P December 2016 59 Index Notes...