Rockwell Automation Publication 1502-UM060A-EN-P - October 2020
21
Chapter
3
Installation
Mounting
The electrically held and the mechanically latched contactors are fixed-
mounted in the cabinet. Two retaining tabs at the rear of the molded base can
be used for mounting. The two mounting slots at the front of the molded base
secure the contactor with 1/4 in. bolts. The appropriate mounting configuration is
provided inside the power cells of Allen-Bradley controllers. If the contactor is
supplied as an OEM component for installation in a custom application, refer to
the dimensional information in
. If the contactor is mounted in an
enclosure designed by an OEM, there must be a minimum of 3 in. (76 mm) of air
space between live parts (terminals and vacuum bottles) and the enclosure.
Figure 6 - Contactor Mounting Details (in. [mm])
8.64 [219]
4.96 [126]
8.53 [217]
0.37
[9]
0.91
[23]
13.22 [336]
0.75 [19]
17.24
[438]
5.00
[127]
3.15 [80]
4.25 [108]
4.25 [108]
8.00 [203]
0.98 [25]
2.12 [54]
10.50 [267]
1.36 [35]
0.281 [7]
wide slots
7.87 [200]
0.37 [9]
Front View
Cutaway View
Bottom View
Содержание Allen-Bradley G Series
Страница 1: ...Medium Voltage 450 A Contactor Series G Bulletin Number 1502 User Manual Original Instructions ...
Страница 6: ...6 Rockwell Automation Publication 1502 UM060A EN P October 2020 Notes ...
Страница 16: ...16 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 1 Product Description Notes ...
Страница 20: ...20 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 2 Receiving and Handling Notes ...
Страница 48: ...48 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 4 Maintenance Notes ...
Страница 50: ...50 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 5 Troubleshooting Notes ...