Rockwell Automation Publication 1512A-UM101B-EN-P - December 2021
85
Appendix B ArcShield Plenum Installation Instructions
STEP 3 – Sequence of Final
Assembly
All plenums in a line-up must be mounted to the top of each enclosure and to
the plenum directly beside it before the front duct sections are reattached (see
).
Figure 71 - Sequence of Final Assembly
The End Cover Plate must be mounted on the closed end of the line-up during
the assembly using 5/16 in. hardware (see
left side).
IMPORTANT
Any unused holes must be filled with thread-forming screws.
All gaps must be sealed and filled with silicone.
End Cover Plate