VersaView 5000 Thin Clients, Industrial Computers, and Accessories for Hazardous Locations
To comply with EN 55024 and EN 55032, use the following cable types.
Hazardous Locations
VersaView 5000 devices for hazardous locations are suitable for these location categories.
Cable Type
Required Attribute
Cable Type
Required Attribute
LAN
Shielded
Line out
Unshielded
USB
Line in
Serial RS-232
Microphone
DVI
DC power
DisplayPort
Mini-DisplayPort
HDMI
VGA
Cat. Nos.
(1)
(1)
Conditions for Safe Use
The following applies to VersaView 5000 thin client and industrial computers for hazardous locations:
• The equipment shall only be used in an area of not more than Pollution Degree 2, as defined in EN 60664-1.
• The equipment shall be installed in a tool-only accessible enclosure that provides a degree of protection not less
than IP54 in accordance with EN 60079-0.
• Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at
the supply terminals to the equipment.
• The internal enclosure ambient temperature range is -20…+60 °C (-4…+140 °F).
Region
Rating
Temperature Range
6200P-NS3A1,
6200P-NS3A1K,
6200P-NS3B1,
6200P-NS3B1K,
6200P-NS3C1,
6200P-NS3C1K,
6200P-NS3C6,
6200T-NA,
6200T-NAK
United States
Class I Division 2, Groups A, B, C, D T4
-20 °C ≤ T
a
≤ +60 °C
(2)
(-4 °F ≤ T
a
≤ +140 °F)
(2) These ThinManager thin client and industrial computers for hazardous locations are required to be mounted in a
restricted access location.
Class I Zone 2, IIC, T4
Canada
Class I Division 2, Groups A, B, C, D T4
Class I Zone 2, IIC, T4
Europe (ATEX)
II 3 G, Ex ec IIC T4 Gc,
DEMKO 19 ATEX 2252 X