16
Industrial Performance Monitors
Rockwell Automation Publication 6186M-IN002C-EN-P - December 2011
Mount the Monitor in a Rack
Follow these directions to mount the monitor.
1.
Place the 1200M, 1500M, or 1700M monitor in the rack adapter (
) and attach it to
the rack adapter with the mounting clips provided (
).
2.
Secure the adapter to the cabinet by installing screws through the holes in the adapter,
and into the mounting rails (
).
IMPORTANT
The mounting rails that run vertically along the inside edges of the front opening of an
EIA-rack cabinet can be of two types: wide or universal.
•
Wide rails have holes spaced 12.7 mm (0.5 in.) and 31.8 mm (1.25 in.) on centers, in a
repeating pattern. Wide rails are prevalent in Europe.
•
Universal rails have holes spaced 12.7 mm (0.5 in.), 15.9 mm (0.625 in.), and 31.8 mm
(1.25 in.) on centers, in a repeating pattern. The universal rails have a hole pattern that
contains the wide pattern but provides an additional hole at the midpoint of the
pattern. Universal rails are prevalent in the United States.
Rear side of
rack adapter
Mounting rail