Chapter 6 Troubleshoot the System
Troubleshooting
If your terminal does not startup correctly, check for adequate power, observe
the splash screen state message and status code, indicator states, or an
application that is not running during power-up.
Determine what changed since the last time the terminal ran normally and
decide if the change can be reversed.
Check for Adequate Power
A terminal that does not receive adequate power could cause unpredictable
behavior. Verify the power requirements in the Specifications table.
Alert
2087
Enable Serial port. Confirm Restart?
Press Yes to restart the terminal.
Alert
2088
Disable Serial port. Confirm Restart?
Press Yes to restart the terminal.
Alert
2089
Cannot disable both communication port.
Make sure at least one communication port is enabled.
Alert
2090
Invalid Control password.
Password must contain at least one special character.
Alert
2091
VNC Server is Disabled.
Enable VNC Server to change/reset password.
Alert
2092
Ethernet port is disabled.
Go to Port Settings on the terminal to enable the Ethernet port.
Alert
2093
Serial port is disabled.
Go to Port Settings on the terminal to enable the Serial port.
Alert
2094
Existing VNC client connection will be terminated. Confirm (Y/N)? Press Yes to terminate the VNC connection, or No to cancel.
Alert
2095
Cannot edit recipe for running application.
Unload the application and try again.
Alert
2096
Recipe with the same name already exists
Make sure the recipe name is unique.
Alert
2097
Recipe Name cannot contain more than 31 characters. Choose
another name.
Make sure the recipe name does not exceed 31 characters.
Alert
2098
The Name cannot be blank and must contain only alphanumeric
characters plus [ $'@!()_- ].
Make sure the name contains only alphanumeric characters plus
[ $'@!()_- ].
Alert
2099
Deletion of a recipe in a design secured application is not allowed.
Copy or Edit Recipes on page 22
Make sure the application is not design secured.
Alert
2100
Renaming of a recipe in a design secured application is not
Copy or Edit Recipes on page 22
Make sure the application is not design secured.
Alert
3001
Available memory is too low to run the application.
Try to release some memory or this may lead to fatal error.
Multilanguage
8193
Language switch ignored. Application was not configured with
new language. An attempt was made to switch to a language that
is not configured for this application.
Either add the specified language and associated strings or remove
the unconfigured language selection.
PanelView 800 Terminal Alerts (Continued)
Category
ID
Description
Corrective Action
Содержание Allen-Bradley 2711R-T10T
Страница 8: ...8 Rockwell Automation Publication 2711R UM001H EN E April 2021 Table of Contents Notes...
Страница 16: ...16 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 1 Overview Notes...
Страница 44: ...44 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 2 Configure the Terminal Notes...
Страница 94: ...94 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 5 Virtual Network Computing Notes...
Страница 106: ...106 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 6 Troubleshoot the System Notes...
Страница 118: ...118 Rockwell Automation Publication 2711R UM001H EN E April 2021 Appendix B Upgrade Firmware Notes...
Страница 122: ...122 Rockwell Automation Publication 2711R UM001H EN E April 2021 Appendix C Install and Replace Components Notes...
Страница 156: ...156 Rockwell Automation Publication 2711R UM001H EN E April 2021 Index Notes...
Страница 157: ...Rockwell Automation Publication 2711R UM001H EN E April 2021 157 PanelView 800 HMI Terminals User Manual...