Programming and Parameters
3-15
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
A051 -
A054
Options
(Cont.)
13 “10V In Ctrl”
Selects 0-10V or ±10V control as the frequency reference.
Start source is not changed.
14 “20mA In Ctrl”
Selects 4-20mA control as the frequency reference. Start
source is not changed.
15 “PID Disable”
Disables PID function. Drive uses the next valid non-PID
speed reference.
16 “MOP Up”
[Internal Freq] at the current
Accel rate if P038 [Speed Reference] is set to 1
“InternalFreq”.
For IP20 rated drives, the default for A069 is 60.0 Hz.
For IP66, NEMA/UL Type 4X drives, the default for A069 is
0.0 Hz.
17 “MOP Down”
Decreases the value of
[Internal Freq] at the current
Decel rate if P038 [Speed Reference] is set to 1
“InternalFreq”.
For IP20 rated drives, the default for A069 is 60.0 Hz.
For IP66, NEMA/UL Type 4X drives, the default for A069 is
0.0 Hz.
18 “Timer Start”
Clears and starts the timer function. May be used to control
the relay or opto outputs.
19 “Counter In”
Starts the counter function. May be used to control the relay
or opto outputs.
20 “Reset Timer”
Clears the active timer.
21 “Reset Countr”
Clears the active counter.
22 “Rset Tim&Cnt”
Clears the active timer and counter.
23 “Logic In1”
Logic function input number 1. May be used to control the
relay or opto outputs (see parameters
,
Options 11-14). May be used in conjunction with StepLogic
parameters
[Stp Logic x].
24 “Logic In2”
Logic function input number 2. May be used to control the
relay or opto outputs (see parameters
,
Options 11-14). May be used in conjunction with StepLogic
parameters
[Stp Logic x].
25 “Current Lmt2”
When active,
[Current Limit 2] determines the drive
current limit level.
26 “Anlg Invert”
Inverts the scaling of the analog input levels set in
[Anlg In 0-10V Lo] and
[Anlg In 0-10V Hi] or
[Anlg In4-20mA Lo] and
[Anlg In4-20mA Hi].
27 “EM Brk Rlse”
If EM brake function is enabled, this input releases the brake.
!
ATTENTION:
If a hazard of injury due to movement of equipment or
material exists, an auxiliary mechanical braking device must be used.
22B-UM001.book Page 15 Tuesday, May 30, 2017 5:22 PM