background image

Rockwell Automation Publication 1794-IN049E-EN-P - May 2022

9

FLEX I/O 2-input Frequency Modules Installation Instructions

Diagnostics

The frequency input module returns diagnostics to the controller processor in word 5 of the BTR file. These diagnostics give you information on the status or condition of the module.

BTR Word 5

Table 4 - Status Indicators Description

Indicator

Condition

Operating Description

Input (0, 1)

(Freq, or Gate)

Off (Dark)

Input Turned Off, Input Not Used, or Wire Disconnected

On (Yellow)

Input Turned On (Active High or Active Low if Inverted)

Fault (F)

(Freq, or Gate)

Off (Dark)

Wire Connected, Normal Operation or Detection Disabled

On (Red Flashing)

Wire Disconnected, Fault Condition (for IEC 1+ Proximity switch or switch contacts with shunt resistor)

Output Alarm

(0, 1)

Off (Dark)

Output Alarm Turned Off

On (Yellow)

Output Alarm Turned On (Logic Drive On)

Status (OK)

Off (Dark)

24V Power Turned Off, or 5V Logic Power Problem

Solid Green

Module OK, Normal Operating Mode

Solid Red

Module Fault, Outputs Disabled

Table 5 - Diagnostic Bit Definition

Input Word

Bit

03

02

01

00

Definition

Word 5

Bits 

00...03

0

0

0

0

0  =  Normal  Operation  (No  Failure)

0

0

0

1

1 = Calibration Failure

0

0

1

0

2 = Configuration Failure

A Minimum Frequency Sample Time value other than 0…9 was selected. 

0

0

1

1

3  =  Message  Failure

0

1

0

0

4 = Lead Break Detection Hardware Failure

0

1

0

1

5 = Major Hardware Failure

0

1

1

0

6 = EEPROM Failure

0

1

1

1

7  =  RAM  Failure

1

0

0

0

8  =  ROM  Failure

1

0

0

1

9 = Calculation Failure

The actual Frequency is greater than 32,767 Hz or 3,276.7 Hz (overange). The scaled Frequency 

is greater than 32,767 Hz or 3,276.7 Hz (overange). The % Full Scale calculation (based on Max 

Frequency) is > 3,276.7%.

1010...1111

10...15 = Not used

Diagnostic Status - indicates the response from the module; a normal or non-normal operating condition.

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

word 5

See 

Table 5

 for diagnostics

Содержание Allen-Bradley 1794-IJ2

Страница 1: ...Hazardous Location Approval 4 North American Hazardous Location Approval 4 Install Your Frequency Input Module 5 Connecting Wiring for the 1794 TB3G and 1794 TB3GS Terminal Base Unit 5 Resolution and...

Страница 2: ...documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installa...

Страница 3: ...s nonhazardous before proceeding WARNING If you connect or disconnect wiring while the field side power is on an electrical arc can occur This could cause an explosion in hazardous location installati...

Страница 4: ...ust be used only with ATEX IECEx certified Rockwell Automation backplanes Secure any external connections that mate to this equipment by using screws sliding latches threaded connectors or other means...

Страница 5: ...d evenly to seat the module in the terminal base unit The module is seated when the latching mechanism 7 is locked into the module Connecting Wiring for the 1794 TB3G and 1794 TB3GS Terminal Base Unit...

Страница 6: ...annel 1 A 11 A 12 A 7 A 5 A 3 A 8 A 10 A 12 6V AC Vortex A 2 A 1 A 3 A 13 A 14 A 12 3V AC Vortex A 2 A 0 A 3 A 13 A 15 A 12 Gate 24V DC IEC 1 Proximity 3 4 B 24 B 23 B 20 B 25 B 26 B 29 24V DC Contact...

Страница 7: ...1 8 0 0002 200 0 0002 0 0225 0 0227 0 1 0 7 1 7 0 0001 500 0 00008 0 0225 0 02258 0 1 0 7 1 7 0 00004 1000 0 00004 0 0225 0 02254 0 1 0 7 1 7 0 00002 Table 2 Input Map Bit 15 14 13 12 11 10 09 08 07 0...

Страница 8: ...module is in a Faulted condition internal error Table 3 Output Map Dec 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Oct 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 0 CF SSM FR CH 0 Number of pulses to terminate...

Страница 9: ...Logic Drive On Status OK Off Dark 24V Power Turned Off or 5V Logic Power Problem Solid Green Module OK Normal Operating Mode Solid Red Module Fault Outputs Disabled Table 5 Diagnostic Bit Definition...

Страница 10: ...re off detection 0 4 mA for proximity encoder or contact switch with 50 k shunt resistor Frequency input impedance 5 k for 50 mV Extended Magnetic Pickup 5 k for 500 mV Magnetic Pickup 10 k for 3V Vor...

Страница 11: ...0 1 2 yellow status indicators Out 0 Out 1 logic side Keyswitch Position 1 Wire size Determined by installed terminal base Wiring category 1 2 on signal ports 3 on power ports Wire type Shielded on s...

Страница 12: ...ents EN 60079 15 Potentially Explosive Atmospheres Protection n II 3 G Ex nA IIC T4 Gc DEMKO 14 ATEX 1342501X IECEx IECEx System compliant with IEC 60079 0 General Requirements IEC 60079 15 Potentiall...

Страница 13: ...Rockwell Automation Publication 1794 IN049E EN P May 2022 13 FLEX I O 2 input Frequency Modules Installation Instructions Notes...

Страница 14: ...be collected separately from any unsorted municipal waste Rockwell Automation Support Use these resources to access support information Documentation Feedback Your comments help us serve your documen...

Отзывы: