284
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Appendix F I/O Tag Definitions
1715-IF16
This section describes the tags that are associated with the 1715-IF16 module.
ModBFieldPowerVoltage2
DINT
Reports the voltage from the field power supply for the specified module and field power input.
Accuracy is ± 500mV
Ch
AB_1715_ChStatusStruc:I:0[8]
Current / Voltage
Status Array
Each element of the array
comprises
Current: REAL
Reports the current for the channel in
milliamps and with an accuracy of ± 2
mA and ± 10% of measurement
Voltage: REAL
Reports the channel voltage at the
output terminals in units of millivolts
and with an accuracy of ± 500 mV (The
voltage element cannot report values
below 0 mV
Table 68 - 8-channel Digital Output, Duplex, Input
Tag Name
Data Type
Definition
Table 69 - 16-channel Analog Input, Simplex, Input
Tag Name
Data Type
Definition
Fault
DINT, Binary
Module fault bit:
0 when one module is present and reporting valid data, OxFFF_FFFF
when no modules are present, no Logix connection exists, or reported
data is invalid.
ChSimplex[0 - 15]
Array of structure
Array of 16 structures that represent the data and fault status for channels 0…15:
Data
REAL
Input data status
Faults
DINT, bit-field
Channel fault status:
Bit
Name
Description
0
Fault
0 = Good
1 = Circuit fault for this channel
3
Underrange
0 = Good
1 = Underrange detected
4
Overrange
0 = Good
1 = Overrange detected
RollingTimestamp
INT
Timestamp data
Status
DINT, bit-field
Bit
Name
Description
8
GroupFault
0 = Good
1 = Any channel on the module is
faulted/failed
Table 70 - 16-channel Analog Input, Duplex, Input
Tag Name
Data Type
Definition
Fault
DINT, Binary
Module fault bit:
0 when one module is present and reporting valid data, OxFFF_FFFF
when no modules are present, no Logix connection exits, or reported
data is invalid.
ChSimplex[0…15]
Array of structure
Array of 16 structures that represent the data and fault status for channels 0…15:
0 = Data
1 = Faults
Data
REAL
Input data
Faults
DINT, bit-field
Channel fault status:
Bit
Name
Description
0
Fault
0 = Good
1 = Circuit fault for this channel
1
ModAFault
0 = Good
1 = This channel on Module A is
faulted/failed
2
ModBFault
0 = Good
Содержание Allen-Bradley 1715-AENTR
Страница 10: ...10 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 114: ...114 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 2 Installation Instructions Notes ...
Страница 134: ...134 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 4 Digital I O Operation Notes ...
Страница 200: ...200 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 6 Configure the Redundant I O System Notes ...
Страница 244: ...244 Rockwell Automation Publication 1715 UM001J EN P December 2020 Chapter 9 Redundant I O System Diagnostics Notes ...
Страница 272: ...272 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix C Reconfigure a Module Online Notes ...
Страница 290: ...290 Rockwell Automation Publication 1715 UM001J EN P December 2020 Appendix G History of Changes Notes ...
Страница 296: ...296 Rockwell Automation Publication 1715 UM001J EN P December 2020 ...
Страница 297: ...Rockwell Automation Publication 1715 UM001J EN P December 2020 297 Redundant I O System User Manual ...