Rockwell Automation Publication 1606-RM101A-EN-P - July 2020
7
AC Input
Attributes
Values
Notes
AC input
Nom
AC 100…240V
Suitable for TN-, TT-, and IT mains networks
AC input range
Min 85…264V
AC
Continuous
operation
Min
264…300V AC
For 500 ms max
Allowed voltage L or N to earth
Max
300V AC
Continuous according to IEC 62477-1
Input frequency
Nom
50…60 Hz
±6%
Turn-on voltage
Typ
80V AC
Steady-state value, see
Shut-down voltage
Typ
70V AC
Typ
55V AC
Dynamic value for 250 ms max
External input protection
—
See recommendations in
External Input Protection on page 27
.
Attributes
Values
Notes
100V AC
120V AC
230V AC
Input current
Typ
2.60 A
2.15 A
1.13 A
At 24V, 10 A, see
Power factor
(1)
(1)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
Typ
0.99
0.99
0.97
At 24V, 10 A, see
Crest factor
(2)
(2) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Typ
1.5 1.5 1.65
At
24V,
10
A
Start-up delay
Typ
300 ms
290 ms
240 ms
See
Rise time
Typ
30 ms
30 ms
30 ms
At 24V, 10 A constant current load, 0 mF load capacitance,
see
Typ
75 ms
75 ms
75 ms
At 24V, 10 A constant current load, 10 mF load capacitance,
see
Turn-on
overshoot
Max
200 mV
200 mV
200 mV
External input
protection
—
See recommendations in
External Input Protection on page 27
.
Figure 1 - Input Voltage Range
Figure 2 - Turn-on Behavior, Definitions
Figure 3 - Input Current vs. Output Current at 24V Output Voltage
Figure 4 - Power Factor vs. Output Current at 24V Output Voltage
Turn-on
85V
Rated
input range
500 ms max
V
IN
P
OUT
300V AC
264V
Shut
-down
Start-up
delay
Rise
Time
O
v
ershoot
- 5%
Output
Voltage
Input
Voltage
12 A
1
2
3
4
5
6
7
8
9
0
0.5
1.0
1.5
2.0
2.5
3A
Input Current, typ.
10 11
a) 100V AC
b) 120V AC
c) 230V AC
b
a
c
Output Current
Power Factor, typ
1
2
3
4
5
6
7
8
9
12 A
0.75
0.8
0.85
0.9
0.95
1.0
10 11
Output Current
(a) 100V AC,
(b) 120V AC,
(c) 230V AC
(a)
(b)
(c)