background image

Rockwell Automation Publication 1606-RM100A-EN-P - July 2020

9

Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual

Output

The output provides a SELV/PELV rated voltage, which is galvanically isolated 
from the input voltage.

The output is designed to supply any kind of loads, including capacitive and 
inductive loads. If extreme large capacitors, such as EDLCs (electric double 
layer capacitors or ‘Ultra Caps’) with a capacitance > 0.3 F are connected to the 
output, the unit can charge the capacitor in an intermittent mode.

The output is electronically protected against overload, no-load, and 
short-circuits. If there is a protection event, audible noise can occur.

Attribute

Value

Notes

Output voltage

Nom

24V

Adjustment range

Min

24…28V

Guaranteed value

Max

30.0V

This is the maximum output voltage that can occur at the clockwise end position of the 
potentiometer due to tolerances. It is not a guaranteed value that can be achieved

Factory  settings

Typ

24.1V

±0.2%, at full load and cold unit

Line  regulation

Max

10 mV

Between  85V and 300V AC

Load  regulation

Max

50 mV

Between 0 A and 6 A, static value, see 

Figure 8

Ripple and noise voltage

Max

50 mVpp

Load > 0.2 A, Bandwidth 20 Hz to 20 MHz, 50 Ohms

Max

200 mVpp

Load < 0.2 A, Bandwidth 20 Hz to 20 MHz, 50 Ohms

Output current

Nom

6 A

(1)

Nom

5 A

Nom

3.8 A

Nom

5.1 A

Nom

4.3 A

Nom

3.2 A

Derate linearly 45…70 °C (113…158 °F)

Fuse breaking current

Typ

15 A

Up to 12 ms once every 5 seconds, see 

Figure 9

. The fuse braking current is an enhanced 

transient current that helps to trip fuses on faulty output branches. The output voltage stays 
above 20V.

Overload behavior

Continuous current

For output voltage above 13V DC, see 

Figure 8

Intermittent current

(2)

For output voltage below 13V DC, se

Figure 8

Overload/short-circuit current

Max

7.2 A

Continuous current, see 

Figure 8

Typ

9 A

Intermitter current peak value for Typ 1 s.
Load impedance 50 mΩ, see 

Figure 10

 Discharge current of output capacitors is not included

Max

3.5 A

Intermitter current average value (R.M.S.) Load impedance 50 mΩ, see 

Figure 10

Output capacitance

Typ

1800 μF

Included inside the power supply

Max

35V

The unit is resistant and does not show malfunctioning when a load feeds back voltage to the 
power supply. It does not matter whether the power supply is on or off. The absorbing energy 
can be calculated according to the built-in large sized output capacitor.

(1)

This current is also available for temperatures up to +70°C (+158 °F) with a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.

(2) At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 1s. After this, the output is switched off for approx. 9s before a new start 

attempt is automatically performed. This cycle is repeated as long as the overload exists. If the overload has been cleared, the device will operate normally. See 

Figure 10

Figure 8 - Output Voltage Versus Output Current, Typ

Figure 9 - Dynamic Output Current Capability, Typ

Output Voltage

0

6

0

7

8

4

8

12

28V

16

20

24

10A

4

1

2

5

9

3

Adjustment

Range

Output Current

A: continuous current

B: intermittent current

A

B

Output Voltage 

(dynamic behavior, < 12ms)

0

0

4

8

12

28V

16

20

24

25 A

10

5

15

20

2.5

7.5

12.5

17.5

22.5

Adjustment

Range

Output Current

Содержание Allen-Bradley 1606-XLE120E

Страница 1: ...Power Supply 24V 5 A 120 W Single phase Input Catalog Numbers 1606 XLE120E 1606 XLE120EC 1606 XLE120EL 1606 XLE120EH 1606 XLE120ED Reference Manual Original Instructions ...

Страница 2: ...ockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations Labels may also be on or inside the equipment to provide spe...

Страница 3: ...ime 10 DC OK Relay Contact 10 Efficiency and Power Losses 11 Functional Diagram 11 Front Side and User Elements 12 Connection Terminals 12 Lifetime Expectancy 14 Mean Time Between Failure MTBF 14 EMC 15 Environment 16 Safety and Protection Features 17 Dielectric Strength 17 Approvals and Fulfilled Standards 19 Regulatory Compliance 19 Physical Dimensions and Weight 20 Accessories 21 Application No...

Страница 4: ...4 Rockwell Automation Publication 1606 RM100A EN P July 2020 Notes ...

Страница 5: ...mall size high efficiency electronic inrush current limitation active power factor correction and a wide operational temperature range The devices have a power reserve of 20 included which can even be used continuously at temperatures up to 45 C 113 F Additionally they can deliver three times the nominal output current for 12 ms that helps to trip fuses on faulty output branches High immunity to t...

Страница 6: ...old up time 35 35 ms At 120 230V AC Temperaturerange 25 70 C 13 158 F Size WxHxD 32x124x102 mm 1 26x4 88x4 02 in Without DIN rail Weight 440 g 0 97 lb Power Supply Connection 1606 XLE120E Screwterminals 1606 XLE120EC Screw terminals and conformalcoatedpc boards 1606 XLE120EL Spring damp terminals 1606 XLE120EH Push in terminals 1606 XLE120ED Screwterminalsand enhanced DC input Term Definition PE a...

Страница 7: ...igure 1 External input protection See Installation Instructions on page 6 AC 100V AC 120V AC 230V Inputcurrent Typ 1 30 A 1 09 A 0 60 A At 24V 5 A see Figure 3 Powerfactor Typ 0 99 0 98 0 91 At 24V 5 A see Figure 4 Crest factor Typ 1 7 1 8 2 2 At 24V 5 A The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform Startup delay Typ 420 ms 380 ms 385 ms Se...

Страница 8: ...6 XLE120EH DC 110 1300V 20 For 1606 XLE120ED DC input range Min 88 180V DC Continuous operation for 1606 XLE120E 1606 XLE120EC 1606 XLE120EL 1606 XLE120EH 88 360V DC Continuous operation for 1606 XLE120ED DC input current Typ 1 21 A At 110V DC at 24V 5 A Typ 0 43 A At 300V DC at 24V 5 A Allowed Voltage or input to Earth Max 360V DC Continuous according to IEC 60664 1 Turn on voltage Typ 74V DC Ste...

Страница 9: ...ip fuses on faulty output branches The output voltage stays above 20V Overloadbehavior Continuouscurrent For output voltage above 13V DC see Figure 8 Intermittent current 2 For output voltage below 13V DC see Figure 8 Overload short circuit current Max 7 2 A Continuouscurrent see Figure 8 Typ 9 A Intermitter current peak value for Typ 1 s Load impedance 50 mΩ see Figure 10 Discharge current of out...

Страница 10: ... Figure 11 Min 55 ms 55 ms 55 ms At 24V 2 5 A see Figure 11 Typ 35 ms 35 ms 35 ms At 24V 5 A see Figure 11 Min 27 ms 27 ms 27 ms At 24V 5 A see Figure 11 Figure 11 Hold up Time Versus Input Voltage Figure 12 Shutdown Behavior Definitions 0 15 30 45 60 90 ms 90 120 155 190 230V AC Input Voltage 75 Hold up Time a b c d c 24V 5 A typ d 24V 5 A min a 24V 2 5 A typ b 24V 2 5 A min 5 Hold up Time Zero T...

Страница 11: ...e time 75 of the nominal load for another 25 of the time and with 100 of the nominal load for the rest of the time Figure 14 Efficiency Versus Output Current at 24V Typ Figure 15 Losses Versus Output Current at 24V Typ Figure 16 Efficiency Versus Output Current at 24V 5 A Typ Figure 17 Losses Versus Output Current at 24V 5 A Typ Efficiency 1 2 3 5 6 A 89 90 91 92 93 94 95 Output Current 4 a b c a ...

Страница 12: ...diode LED green On when the output voltage is 90 of the adjusted output voltage 5 DC OK Relay Contact The DC OK relay contact is synchronized with teh DC OK light emitting diode LED See DC OK Relay Contact on page 10 1 2 3 4 5 1 2 3 4 5 Figure 20 1606 XLE120EH Figure 21 1606 XLE120ED User Elements 1 Input Terminals N L N L Line Input PE Protective Earth Input 2 Output Terminals Two identical poles...

Страница 13: ...ick connectspring clamp termination Quick connectspring clamp termination Push intermination Solid wire Max 6 mm2 Max 6 mm2 Max 1 5 mm2 Stranded wire Max 4 mm2 Max 4 mm2 Max 1 5 mm2 American Wire Gauge AWG 20 10 AWG 20 10 AWG 24 16 Wire diameter max including ferrules 2 8 mm 0 11in 2 8 mm 0 11 in 1 6 mm 0 06 in Wire stripping length 10 mm 0 4 in 10 mm 0 4 in 7 mm 0 28 in Screwdriver 3 0 mm 0 12 in...

Страница 14: ...is a statistical representation of the likelihood of a device to fail An MTBF figure of for example 1 000 000 hr means that statistically one unit will fail every 100 hours if 10 000 units are installed in the field However it cannot be determined if the failed unit has been running for 50 000hr or only for 100 hr For these types of units the MTTF Mean Time To Failure value is the same value as th...

Страница 15: ...C Okay Signal to PE 1 kV Criterion A Conducteddisturbance EN 61000 4 6 0 15 80 MHz 20V Criterion A 0 of 100V AC 0V AC 20 ms Criterion A 40 of 100V AC 40V AC 200 ms Criterion C 70 of 100V AC 70V AC 500 ms Criterion A 0 of 100V AC 0V AC 20 ms Criterion A 40 of 100V AC 80V AC 200 ms 4 A Criterion A 40 of 100V AC 80V AC 500 ms 4 A Criterion C 70 of 100V AC 140V AC 20 ms Criterion A Voltage interruptio...

Страница 16: ...60 ft Degree of pollution 2 According to IEC 62477 1 not conductive Vibration sinusoidal 2 17 8Hz 1 6mm 17 8 500Hz 2 g 2 hours axis According to IEC 60068 2 6 Shock 30 g 6 ms 20 g 11 ms 3 bumps per direction 18 bumps in total Accordingto IEC60068 2 27 Shock and vibration are tested in combination with DIN rails according to EN 60715 with a height of 15 mm 0 59 in and a thickness of 1 3 mm 0 05 in ...

Страница 17: ...C Max 32 0V DC In case of an internal anomaly a redundant circuit limits the maximum output voltage The output shuts down and performs three restart attempts If the failure continues the output shuts down Cycle input power to reset Class of protection I According to IEC 61140 A PE Protective Earth connection is required Degree of protection IP 20 According to EN IEC 60529 Over temperature protecti...

Страница 18: ...Input Reference Manual Figure 26 Dielectric Strength 1 When testing inputs to DC OK confirm that the maximal voltage between DC OK and the output is not exceeded column D We recommend connecting DC OK pins and the output pins together when performing the test D A C B B 1 N L Input DC ok Earth PE Output ...

Страница 19: ...ontrol and Laboratory Use Particular requirements for control equipment Applicable for US and Canada NMTR 7 E56639 IND CONT EQ CE EU Declaration of Conformity Trade conformity assessment for Europe The CE marking indicates conformance with the European RoHS directive EMC Directive and the Low voltage directive LVD REACH Directive Manufacturer s Statement EU Regulation regarding the Registration Ev...

Страница 20: ...Weight 440 g 0 97 lb DIN rail Use 35 mm 1 38 in DIN rails according to EN 60715 or EN 50022 with a height of 7 5 mm or 15 mm 0 3 in or 0 6 in Housing material Body Aluminum alloy Cover Zinc platedsteel Installation clearances See Installation Instructions on page 6 Penetrationprotection Small parts like screws nuts etc with a diameter larger than 3 5 mm 0 14 in Figure 27 Front View Approximate Dim...

Страница 21: ...with two 10 A nominal input channels which are individually decoupled by utilizing diode technology The output can be loaded with a nominal 20 A continuous current The device does not require an additional auxiliary voltage and is self powered even if there is a short circuit across the output For a safe and vibration resistant wiring the device is equipped with time saving quick connect spring cl...

Страница 22: ...dant systems The device is equipped with two input channels each rated for 10 A for ambient temperatures up to 70 C 158 F and are individually decoupled by utilizing MOSFET technology The inputs can also be operated up to 12 A when the ambient temperature does not exceed 45 C 113 F The output can be loaded with nominal 20 A at 70 C 158 F or 24 A at 45 C 113 F continuous current Using MOSFETSs inst...

Страница 23: ...current Solenoids contactors and pneumatic modules often have a steady state coil and a pick up coil The inrush current demand of the pick up coil is several times higher than the steady state current and usually exceeds the nominal output current The same situation applies when starting a capacitive load The peak current capability also delivers the safe operation of subsequent circuit breakers o...

Страница 24: ...voltage should be set to the following at these ambient temperatures 27 8V at 10 C 50 F 27 5V at 20 C 68 F 27 15V at 30 C 86 F 26 8V at 40 C 104 F Series Operation Devices of the same type can be connected in series for higher output voltages It is possible to connect as many units in series as needed providing the sum of the output voltage does not exceed 150V DC Voltages with a potential above O...

Страница 25: ... or circuit breaker with a rating of 10 A is required on each output Alternatively a diode or redundancy module can also be utilized Energize all devices simultaneously It can be necessary to cycle the input power turn off for at least 5 seconds if the output was in overload or short circuits and the required output current is higher than the current of one unit Keep an installation clearance of 1...

Страница 26: ...58 F Pay attention that leakage current EMI inrush current harmonics will increase when using multiple devices Recommendations for building redundant power systems Use separate input fuses for each device Use separate mains systems for each device whenever it is possible Monitor the individual devices Therefore use the DC OK signal of the device It is desirable to set the output voltages of all de...

Страница 27: ...Manual Figure 38 1 1 Redundant Configuration for 5 A Load Current with a Dual Redundancy Module Figure 39 1 1 Redundant Configuration with Active Load Share for 5 A Load Current With a Dual Redundancy Module Figure 40 N 1 Redundant Configuration for 15 A Load Current with Multiple Power Supplies and Redundancy Modules ...

Страница 28: ... power supply The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure The power supply is placed in the middle of the box no other heat producing items are inside the box The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of 10 mm 0 39 in The following measurement results can...

Страница 29: ...in the maximum allowed ambient temperature The listed lifetime and MTBF values from this datasheet apply only for the standard mounting orientation The following curves give an indication for allowed output currents for altitudes up to 2000 m 6560 ft Figure 41 Mounting Orientation A Standard Orientation Figure 42 Mounting Orientation B Upside Down Figure 43 Mounting Orientation C Table top Mountin...

Страница 30: ...30 Rockwell Automation Publication 1606 RM100A EN P July 2020 Power Supply 24V 5 A 120 W Single phase Input Reference Manual Notes ...

Страница 31: ...es a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application Installation and Maintenance of Solid state Control publication SGI 1 1 Designed to harmonize with NEMA Standards Publication No ICS 1 1 1987 and provides general guidelines for the application installation and maintenance of solid state control in the form of individual ...

Страница 32: ...rticles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installation instructions manuals brochures and technical data publications rok auto literature Product Compatibility and Download Center PCDC Download firmware associated files such as AOP EDS and DTM and access product release notes rok a...

Отзывы: