Rockwell Automation Publication 1606-RM109A-EN-P - August 2020
15
Power Supply —12V, 10 A, 120 W, Single Phase
Connection Terminals
The terminals are IP20 Finger safe constructed and suitable for field- and
factory wiring.
Daisy Chaining
Daisy chaining (jumping from one power supply output to the next) is allowed
as long as the average output current through one terminal pin does not
exceed 25 A. If the current is higher, use a separate distribution terminal block
as shown in
Input
Output
DC OK Signal
Terminal Type
Screw termination
Screw termination
Push-in termination
Solid wire, Max
6 mm
2
6 mm
2
1.5 mm
2
Stranded wire, Max
4 mm
2
4 mm
2
1.5 mm
2
American Wire Gauge
AWG 20…10
AWG 20…10
AWG 24…16
Max wire diameter (including ferrules) 2.8mm (0.11 in.)
2.8 mm (0.11 in.)
1.6 mm (0.06 in.)
Recommended tightening torque
1 N•m (9 lb•in)
1 N•m (9 lb•in)
-
Wire stripping length
7 mm (0.28 in.)
7 mm (0.28 in.)
7 mm (0.28 in.)
Screwdriver
3.5 mm (.137 in.) slotted
or cross- head No 2
3.5 mm (.137 in.) slotted
or cross- head No 2
3.5 mm (.137 in.) slotted
to open the spring
Figure 19 - Daisy Chaining of Outputs
Figure 20 - Using Distribution Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
Max 25 A continuous
Distribution
Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output