Rockwell Automation Publication 1606-RM109A-EN-P - August 2020
7
Power Supply —12V, 10 A, 120 W, Single Phase
AC Input
The device is suitable to be supplied from TN, TT, or IT mains networks with
AC voltage. For suitable DC supply voltages, see
Attribute
Value
Notes
AC input
Nom
AC 100…240V
—
AC input range
Min
85…264V AC
Continuous operation
Min
264…300V AC
Occasionally for maximal 500 ms
Allowed voltage L or N to earth Max
300V AC
Continuous, according to IEC 606641
Input frequency
Nom
50…60 Hz
±6%
Turn-on voltage
Typ
80V AC
Steady-state value. See
.
Shut-down voltage
Typ
74V AC
Steady-state value, See
.
External input protection
—
AC 100V
AC 120V
AC 230V
Input current
Typ
1.30 A
1.09 A
0.60 A
At 12V, 10ASee
Power factor
Typ
0.99
0.98
0.91
At 12V, 10 A See
,
Crest factor
Typ
1.7
1.8
2.2
At 12V, 10 A The crest factor is the
mathematical ratio of the peak value
to RMS value of the input current
waveform.
Startup delay
Typ
400 ms
350 ms
375 ms
Rise time
Typ
30 ms
30 ms
30 ms
At 12V, 10 A const. current load, 0mF
load capacitance. See
Typ
50 ms
50 ms
50 ms
At 12V, 10 A const. current load, 10mF
load capacitance
.
Turn-on overshoot Max
200 mV
200 mV
200 mV
Figure 1 - Input Voltage Range
Figure 2 - Turn-on Behavior, Definitions
Figure 3 - Input Current Versus Output Current at 12V Output Voltage
Figure 4 - Power Factor Versus Output Current at 12V Output Voltage
Turn-on
85V
Rated
input range
max.
500 ms
V
IN
P
OUT
300V AC
264V
Shut
-down
Start-up
Rise
delay
Time
Oversh
o
ot
- 5%
Output
Voltage
Input
Voltage
12 A
1
2
4
6
8
0
0.25
0.5
0.75
1.0
1.25
1.5 A
Input Current, typ
10
a) 100V AC
b) 120V AC
c) 230V AC
Output Current
(a)
(b)
(c)
Power Factor, typ
2
4
6
8
10
12 A
0.75
0.8
0.85
0.9
0.95
1.0
Output Current
(a) 100V AC,
(b) 120V AC,
(c) 230V AC
(a)
(b)
(c)