![Rockwell Automation Allen-Bradley 1606-XLDF240F Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/rockwell-automation/allen-bradley-1606-xldf240f/allen-bradley-1606-xldf240f_reference-manual_1475677014.webp)
14
Rockwell Automation Publication 1606-RM124A-EN-P - September 2021
DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual
Environment
Attributes
Values
Notes
Operational temperature
-25…+70 °C (-13…+158 °F)
The operational temperature is the ambient or surrounding
temperature and is defined as the air temperature 2 cm
(0.79 in.) below the device.
Storage temperature
-40…+85 °C (-40…+185 °F)
For storage and transportation
Output derating
3.2 W/1 °C (3.2 W/1.8 °F)
Between 45…60 °C (113…140 °F)
6 W/1 °C (6 W/1.8 °F)
Between 65…70 °C (140…158 °F)
15 W/1000 m (15 W/3280 ft) or
5 °C/1000 m (9 °F/3280 ft)
For altitudes >2000 m (6562 ft), see
Hardware does not control the derating. You must take this into consideration to stay below the derated
current limits to help prevent overloading the unit.
Humidity
5…95% r.H.
According to IEC 60068-2-30. No condensation allowed.
Atmospheric pressure
110…47 kPa
See
for details
Altitude
Up to 6000 m (19,685 ft)
See
for details
Degree of pollution
2
According to IEC 62477-1, non-conductive
Vibration sinusoidal
(1)
(1) Shock and vibration are tested in combination with DIN rails according to EN 60715, with a height of 15 mm (0.59 in.) and a thickness
of 1.3 mm (0.05 in.). These tests are performed with the DC/DC converter in standard mounting orientation.
2…17.8 Hz: ±1.6 mm (0.063 in.)
17.8…500 Hz: 2 g
2 hours / axis
According to IEC 60068-2-6
Shock
30 g 6 ms, 20 g 11 ms
3 bumps/direction
18 bumps in total
According to IEC 60068-2-27
LABS compatibility
As a rule, only non-silicon precipitating materials are used. The unit conforms to the LABS criteria and is
suitable for use in paint shops.
Corrosive gases
Compliant to ISA-71.04-1985, Severity Level G3 and IEC 60068-2-60 Test Ke Method 4 for a service life of 10
years, minimum, in these environments.
Audible noise
Some audible noise can be emitted from the DC/DC converter during no load, overload, or short circuit.
Figure 19 - Output Power Versus Ambient Temperature
Figure 20 - Output Power Versus Altitude
0
-25
0
20
40
70
1
2
3
4
5
6
60
Ambient Temperature (
°C)
A... Continuous
B... Short term
Allowed Output Current (A) at 48V
A
B
2000 m
4000 m
6000 m
1 A
2 A
3 A
4 A
5 A
6 A
Altitude (Atmospheric Pressure)
Allowed Output Current at 48V
80 kPa
62 kPa
47 kPa
110 kPa
0 m
A... Ambient <60 °C
B... Ambient <45 °C
C... Short term
A
B
C