Rockwell Automation Allen-Bradley 1606-XLB480E Скачать руководство пользователя страница 2

 

Rockwell Automation Support 

For Technical Support, visit ROK.AUTO/SUPPORT. 

The information in this document is believed to be accurate and reliable and may change without notice.

 

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. 
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their companies. 

www.rockwellautomation.com 

Power, Control and Information Solution Headquarters 

Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax. (1) 414.382.4444 
Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgien, Tel: (32) 2663.0600, Fax (32) 2663.0640 
Asia Pacific: Rockwell Automation,Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887.4778, Fax (852) 2508.1846 
Turkey: Rockwell Otomasyon Ticraet A.

Ş

., Kar Plaza 

İş

 Merkezi E Blok Kat:6 34752 

İ

çerenköy, Istanbul, Tel: (90) 216.5698400  (EEE Yönetmeli

ğ

ine Uygundur)

 

Publication 1606-IN064A-EN-E - June 2020

 

DIR 10005140958 (Version 01)

Copyright © 2020 Rockwell Automation, Inc. All Rights Reserved..

 

The isolation of the device is designed to withstand impulse voltages of overvoltage category III according to IEC 
60664-1. 
The device is designed as “Class of Protection” I equipment according to IEC 61140. Do not use without a proper 
PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage between the 
input terminals and the PE potential must not exceed 300Vac. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and 
do not cover ventilation grid! 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) the overvoltage category is 
reduced to level II and a reduction in output current is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side. 
Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device is permanently loaded 
with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 20A without additional protection device. 
For higher branch circuits use an additional protection device. If an external input protection device is utilized, do 
not use one smaller than a 10A B- or 6A C-characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the 
ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any kind of loads, 
including inductive and capacitive loads. If capacitors with a capacitance >3F are connected, the unit might 

charge the capacitor in an intermittent mode. 
Do not apply return voltages from the load to the output terminals higher than 35V. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC-OK LED reports an output voltage above 18V of a running device. 
The DC-OK relay monitors the output voltage of a running device. The contact is closed when the output voltage 
is above 22V. Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output shuts down 
and starts automatically again after cooling off. 
At heavy overloads (when output voltage falls below 13V), the device delivers continuous output current for 2-5s. 
After this, the output is switched off for 7s before a new start attempt with 1s is automatically performed. This 
cycle is repeated as long as the overload exists. 
Do not parallel devices for higher output currents. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many devices in 
series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32V. The output shuts 

down and automatically attempts to restart. 

 

Technical Data - ctd.

 

Max. wire size (litz wire) 

1.5mm²

 

 DC-OK 

terminals 

Wire size AWG 

AWG 24-16 

DC-OK terminals 

Max. wire diameter 

1.6 mm 

DC-OK terminals 

Wire stripping length 

7mm / 0.28inch 

DC-OK terminals 

Size 

(wxhxd)

 

59x124x127mm Without 

DIN-rail 

Weight 

810g / 1.79lb 

 

 

Functional Diagram 

+

+

-

-

Output

Over-

Voltage

Protection

PFC

Converter

Voltage

Regulator

Power

Converter

Output

Filter

Temper-

ature

Shut-

down

Input Fuse
Input Filter
Input Rectifier
Inrush Current
Limiter

V

OUT

L

N

DC-OK

Contact

DC-OK

LED

DC-ok

Relay

13

14

 

 

Output Characteristic 

Output voltage

30A

24V

Output current

13V

0V

5A

10A

15A

25A

0A

Adjustment range

28V

A

B

20A

A: continuous current

B: intermittent current

 

 

Temperature Range 

Allowed output current at 24V

Ambient temperature

0A

-25

20A

0

+70°C

12.5A

+55

 

 