Installation and Wiring
2-7
Long Motor Cable Effects
Reflected Wave Protection
The drive should be installed as close to the motor as possible. Installations with
long motor cables may require the addition of external devices to limit voltage
reflections at the motor (reflected wave phenomena). See Table 2.E for
recommendations.
Important:
Both Reflected Wave and Capacitive Current Considerations need
to be taken into account when determining motor cable lengths
(see Table 2.E and Table 2.F). The use of an external device to
limit reflected wave phenomenon may effect the accuracy of
Bulletin 160 current sensing.
The reflected wave data applies to all frequencies 2 to 8 kHz. For 230V ratings,
the maximum cable length recommendations are the same as the capacitive current
recommendations (see Table 2.F).
Cable Length Recommendations – Reflected Wave
Table 2.E
➊
Cable lengths listed are for PWM frequencies of 2 kHz. Refer to publication 1204-5.1 for cable length recommendations at
other PWM frequencies.
➋
The maximum peak-to-peak voltage of the drive is 1400V due to the minimum on/off time software.
Reflective Wave Testing has been done on cable lengths up to 160 meters (600 feet). See Table 2.F for capacitive current
recommendations.
380-
460V
Ratings
Motor
Insulation
Rating
Motor Cable Only
RWR at Drive
➊
Reactor at Motor
Shielded
Unshielded
Shielded
Unshielded
Shielded
Unshielded
feet
meters feet
meters feet
meters feet
meters feet
meters feet
meters
4.0 kW
(5 HP)
1000 Vp-p
45
13.7
20
6.1
525
160
600
183
325
99.1
300
91.5
1200 Vp-p
90
27.4
40
12.2
525
160
600
183
525
160
425
130
1600 Vp-p
➋
525
160
475
145
525
160
600
183
525
160
600
183
2.2 kW
(3 HP)
1000 Vp-p
40
12.2
40
12.2
525
160
600
183
225
68.6
250
76.2
1200 Vp-p
90
27.4
60
18.3
525
160
600
183
325
99.1
425
130
1600 Vp-p
➋
525
160
500
152
525
160
600
183
525
160
600
183
1.5 kW
(2 HP)
1000 Vp-p
40
12.2
40
12.2
425
130
600
183
325
99.1
300
91.5
1200 Vp-p
90
27.4
60
18.3
425
130
600
183
425
130
450
137
1600 Vp-p
➋
500
152
500
152
425
130
600
183
540
165
600
183
0.75 kW
(1 HP)
1000 Vp-p
55
16.8
40
12.2
325
99.1
600
183
325
99.1
350
107
1200 Vp-p
125
38.1
60
18.3
325
99.1
600
183
500
152
450
137
1600 Vp-p
➋
500
152
500
152
325
99.1
600
183
500
152
600
183
0.55 kW
(0.75 HP)
1000 Vp-p
45
13.7
40
12.2
300
91.5
600
183
300
91.5
300
91.5
1200 Vp-p
125
38.1
60
18.3
300
91.5
600
183
500
152
500
152
1600 Vp-p
➋
500
152
500
152
300
91.5
600
183
500
152
600
183
0.37 kW
(0.5 HP)
1000 Vp-p
45
13.7
90
27.4
300
91.5
425
130
300
91.5
425
130
1200 Vp-p
125
38.1
180
54.9
300
91.5
425
130
500
152
500
152
1600 Vp-p
➋
500
152
500
152
300
91.5
425
130
500
152
500
152
Содержание Allen-Bradley 160 SSC Series
Страница 12: ...1 6 Getting Started End of Chapter ...
Страница 58: ...5 20 Parameters and Programming End of Chapter ...
Страница 66: ...A 4 Specifications End of Chapter ...
Страница 75: ...Accessories and Dimensions B 9 Drilling Template A Figure B 10 ...
Страница 76: ...B 10 Accessories and Dimensions Drilling Template B Figure B 11 ...
Страница 82: ...C 6 CE Conformity End of Chapter ...
Страница 87: ......