58
Rockwell Automation Publication 450L-UM001F-EN-P - March 2022
Chapter 5 System Configuration
shows the function and default settings for the M12 8-pin muting
receiver plug-in (450L-APR-MU-8) inserted in a 450L-E or 450L PAC safety light
curtain transceiver stick; DIP 8 = ON.
450L-APR-UN-8 Connection
Plug-in
shows the function and default settings for the M12 8-pin muting
receiver plug-in (450L-APR-UN-8) inserted in a 450L safety light curtain
transceiver stick.
For the UNIV plug-in: if pin 4 and pin 8 are short circuited (transmitter mode),
the DIP switch settings have no impact on the transmitter functionality.
Table 28 - Function and Default Settings
Switch Number
Switch Function
Default
Description
9
450L-E only
Combination activates one
of the following muting
configurations:
OFF
• DIP 9: OFF, DIP 10: OFF, DIP 11:
OFF:
No muting
• DIP 9: OFF, DIP 10: ON, DIP 11: OFF
2L muting sensors connected to
connection plug-in
• DIP 9: OFF, DIP 10: ON, DIP 11: ON
2L muting sensors connected to
I/O cascading plug-in
• DIP 9: ON, DIP 10: OFF, DIP 11: OFF
2T muting sensors connected to
connection plug-in
• DIP 9: ON, DIP 10: OFF, DIP 11: ON
2T muting sensors connected to
cascading plug-in
• DIP 9: ON, DIP 10: ON, DIP 11: ON
4T muting sensors connected to
cascading plug-in
10
OFF
11
OFF
12
—
OFF
—
Table 29 - Function and Default Settings
Switch Number
Switch Function
Default
Description
1
450L-E only: Software
Configuration
OFF
OFF: Disabled
ON: Enabled
2
Low Range Activation
OFF
OFF: Disabled
ON: Enabled
3
450L-E and 450L PAC only:
Activates Beam Coding
OFF
OFF: Disabled
ON: Enabled
4
450L-E only: Activates
Interference Rejection
OFF
OFF: Disabled
ON: Enabled
5
Combination activates one
of the following start
modes:
• Automatic start
• Manual (re)start
• Manual cold start
• Manual start with off
function
OFF
• DIP 5: OFF, DIP 6 OFF:
Automatic start (Default)
• DIP 5: ON, DIP 6 OFF:
Manual (re)start
• DIP 5: OFF, DIP 6 ON:
Manual cold start
• DIP 5: ON, DIP 6 ON:
Manual start with off
function
6
OFF
7
External Device Monitoring OFF
OFF: Disabled
ON: Enabled
8
—
OFF
—
9
—
OFF
—
10
—
OFF
—
11
—
OFF
—
12
—
OFF
—
Содержание Allen-Bradley 140M
Страница 8: ...8 Rockwell Automation Publication 450L UM001F EN P March 2022 Table of Contents Notes ...
Страница 20: ...20 Rockwell Automation Publication 450L UM001F EN P March 2022 Chapter 2 Safety Concepts Notes ...
Страница 108: ...108 Rockwell Automation Publication 450L UM001F EN P March 2022 Chapter 7 Status Indicators and Troubleshooting Notes ...
Страница 114: ...114 Rockwell Automation Publication 450L UM001F EN P March 2022 Chapter 8 Safety Instructions Notes ...
Страница 184: ...184 Rockwell Automation Publication 450L UM001F EN P March 2022 Appendix B Typical Installations Notes ...
Страница 190: ...190 Rockwell Automation Publication 450L UM001F EN P March 2022 Index ...
Страница 191: ...Rockwell Automation Publication 450L UM001F EN P March 2022 191 GuardShield Safety Light Curtain User Manual ...