1204 Terminator
5
1336 PLUS/FORCE/IMPACT™ Maximum Motor Cable Length Restrictions
(380-480 Volt Drives)
1
Lengths are given in meters and (feet)
NR = Not Recommended
1
Values shown are for 480V nominal input voltage and drive carrier frequency of 2 kHz. Consult factory regarding operation at carrier frequencies above 2 kHz. Multiply
values by 0.85 for high line conditions. For input voltages of 380, 400 or 415V AC, multiply the table values by 1.25, 1.20 or 1.15, respectively.
2
Includes wire in conduit.
Type A Motor Characteristics: No phase paper or misplaced phase paper, lower quality insulation systems, corona inception voltages between 850 and 1000 volts.
Type B Motor Characteristics: Properly placed phase paper, medium quality insulation systems, corona inception voltages between 1000 and 1200 volts.
1329R/L Motors:
These AC variable speed motors are “Power Matched” for use with Allen-Bradley drives. Each motor is energy efficient and designed
to meet or exceed the requirements of the Federal Energy Act of 1992. All 1329R/L motors are optimized for variable speed operation
and include premium inverter grade insulation systems which meet or exceed NEMA MG1. Part 31.40.4.2.
Drive
Frame
Drive kW (HP)
Motor kW (HP)
w/1204-TFB2 Terminator
w/1204-TFA1 Terminator
With Allen-Bradley
1329R/L Motors
Motor Type
Motor Type
A or B
A
B
Cable Type
Cable Type
Cable Type
Shld.
2
Unshld.
Shld.
2
Unshld.
Shld.
2
Unshld.
A1
0.37 (0.5)
0.37 (0.5)
Use 1204-TFA1
Terminator
or 1329R/L Motor
30.5 (100)
61.0 (200) 30.5 (100)
61.0 (200)
For applications/ installations
using new motors, no restric-
tions in lead length due to volt-
age reflection are necessary.
You should observe standard
practices for voltage drop, cable
capacitance, and other issues.
0.75 (1)
0.75 (1)
30.5 (100)
30.5 (100) 30.5 (100)
30.5 (100)
0.75 (1)
0.37 (0.5)
30.5 (100)
61.0 (200) 30.5 (100)
61.0 (200)
A2
1.2 (1.5)
1.2 (1.5)
30.5 (100)
30.5 (100) 61.0 (200)
61.0 (200)
0.75 (1)
30.5 (100)
30.5 (100) 61.0 (200)
61.0 (200)
0.37 (0.5)
30.5 (100)
30.5 (100) 61.0 (200)
61.0 (200)
1.5 (2)
1.5 (2)
91.4 (300)
91.4 (300)
30.5 (100)
30.5 (100) 91.4 (300)
61.0 (200)
1.2 (1.5)
91.4 (300)
182.9 (600)
30.5 (100)
30.5 (100) 91.4 (300)
61.0 (200)
0.75 (1)
182.9 (600)
182.9 (600)
30.5 (100)
30.5 (100) 91.4 (300)
61.0 (200)
0.37 (0.5)
182.9 (600)
182.9 (600)
30.5 (100)
30.5 (100) 91.4 (300)
61.0 (200)
2.2 (3)
2.2 (3)
182.9 (600)
182.9 (600)
Use 1204-TFB2 Terminator
or 1329R/L Motor
1.5 (2)
182.9 (600)
182.9 (600)
0.75 (1)
182.9 (600)
182.9 (600)
0.37 (0.5)
182.9 (600)
182.9 (600)
A3
3.7 (5)
3.7 (5)
182.9 (600)
182.9 (600)
2.2 (3)
182.9 (600)
182.9 (600)
1.5 (2)
182.9 (600)
182.9 (600)
0.75 (1)
182.9 (600)
182.9 (600)
0.37 (0.5)
182.9 (600)
182.9 (600)
A4
5.5-7.5 (7.5-10)
5.5-7.5 (7.5-10)
182.9 (600)
182.9 (600)
B
5.5-22 (7.5-30)
5.5-22 (7.5-30)
182.9 (600)
182.9 (600)
C
30-45 (X40-X60)
30-45 (40-60)
182.9 (600)
182.9 (600)
D
45-112 (60-X150)
45-112 (60-150)
182.9 (600)
182.9 (600)
E
112-187 (150-250)
112-224 (150-300) 182.9 (600)
182.9 (600)
F
187-336 (250-450)
187-336 (250-450) 182.9 (600)
182.9 (600)
G
187-448 (X250-600) 187-448 (250-600) 182.9 (600)
182.9 (600)
H
552-597 (700-800)
522-597 (700-800) 182.9 (600)
182.9 (600)
Содержание Allen-Bradley 1204 Series