Programming and Parameters
3-17
MO
T
O
R CONTR
O
L
To
rq
At
tri
b
ut
es
061 [Autotune]
Provides a manual or automatic method
for setting [IR Voltage Drop] and [Flux
Current Ref], which affect sensorless
vector performance. Valid only when
parameter 53 is set to “Sensrls Vect,” “SV
Economize” or “FVC Vector”
Default:
Options:
3
0
1
2
3
“Calculate”
“Ready”
“Static Tune”
“Rotate Tune”
“Calculate”
“Ready” (0) = Parameter returns to this setting following a “Static Tune” or “Rotate
Tune.” It also permits manually setting [IR Voltage Drop] and [Flux Current Ref].
“Static Tune” (1) = A temporary command that initiates a non-rotational motor
stator resistance test for the best possible automatic setting of [IR Voltage Drop].
A start command is required following initiation of this setting. The parameter
returns to “Ready” (0) following the test, at which time another start transition is
required to operate the drive in normal mode. Used when motor cannot be
rotated.
“Rotate Tune” (2) = A temporary command that initiates a “Static Tune” followed by
a rotational test for the best possible automatic setting of [Flux Current Ref]. A
start command is required following initiation of this setting. The parameter
returns to “Ready” (0) following the test, at which time another start transition is
required to operate the drive in normal mode. Important: Used when motor is
uncoupled from the load. Results may not be valid if a load is coupled to the motor
during this procedure.
“Calculate” (3) = This setting uses motor nameplate data to automatically set [IR
Voltage Drop] and [Flux Current Ref].
062 [IR Voltage Drop]
Value of voltage drop across the
resistance of the motor stator at rated
motor current. Used only parameter 53 is
set to “Sensrls Vect”, “SV Economize” or
“FVC Vector.”
Default:
Min/Max:
Units:
[Motor NP Volts]
×
0.25
0.0/[Motor NP Volts]
×
0.25
0.1 VAC
063 [Flux Current Ref]
Value of amps for full motor flux. Used
only when parameter 53 is set to “Sensrls
Vect”, “SV Economize” or “FVC Vector.”
Default:
Min/Max:
Units:
Drive Rating Based
0.00/[Motor NP FLA]
0.01 Amps
064 [Ixo Voltage Drop]
Value of voltage drop across the leakage
inductance of the motor at rated motor
current. Used only when parameter 53 is
set to “FVC Vector.”
Default:
Min/Max:
Units:
Drive Rating Based
0.0/Motor NP Volts
0.1 VAC
F
ile
Gr
oup
No
.
Parameter Name and Description
See
page 3-2
for symbol descriptions
Values
Re
lated
!
ATTENTION: Rotation of the motor in an undesired direction can
occur during this procedure. To guard against possible injury and/or
equipment damage, it is recommended that the motor be
disconnected from the load before proceeding.
32
2…6
Содержание 9VT201-007HTNNN
Страница 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Страница 4: ...soc 2 ...
Страница 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Страница 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Страница 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Страница 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Страница 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Страница 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Страница 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Страница 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Страница 223: ......