PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
19
Publication 2711P-IN001I-EN-P - November 2009
Connect DC Power
Follow these steps to connect the terminal DC power.
1.
Verify that the terminal is not connected to a power source.
2.
Secure the DC power wires to the terminal block.
Follow the markings on the terminal blocks and the terminal for proper connections.
3.
Secure the earth/ground wire to the earth/ground terminal screw at the bottom of
the display.
DC Power Supply Connections
WARNING
Explosion Hazard - Do not disconnect equipment unless power has been switched off and
area is known to be nonhazardous.
Disconnect all power before installing or replacing components. Failure to disconnect
power may result in electrical shock or damage to the terminal.
GND
2-position Terminal Block
(series E or later logic modules)
3-position Terminal Block
(series A to D logic modules)
+
–
–
+
Earth/Ground to Ground Bus
DC - DC+
DC- DC+
GND