Nominal impedance
14.1 k
Ω
3.74
k
Ω
(isolated)
IEC input compatibility
Type 1
Type 3
Analog Inputs (2080-LC10-12QWB, -12QBB, -12DWD) (Inputs 4 through 7)
Attribute
Value
Input type
DC voltage
Input voltage range
0…10V DC
Input voltage, max
26.4V DC
Value of LSB
2.5 mV
Input resolution
10-bit
Smoothing
None, smoothing
Overall accuracy
5% of full-scale (2% with calibration)
(25…55 °C)
(77…131 °F)
Noise rejection
50/60 Hz
Common mode rejection
40 dB, DC to 60 Hz with Smoothing filter
Nominal impedance
14.1 k
Ω
(non-isolated)
DC Output (2080-LC10-12QBB)
Attribute
Value
User supply voltage, min
10 V DC
User supply voltage, max
26.4V DC
On-state voltage drop
1V @ max load current
2.5V @ max surge current
Current ratings
0.5A @ 55 °C max
1.0A @ 30 °C max
1.0 mA min
Surge current, peak
4.0 A
Surge current, max duration
10 ms
Turn-on- time, max
0.1 ms
Turn-off time, max
0.1 ms
DC Inputs (2080-LC10-12QWB, -12QBB, -12DWD) (Inputs 0 through 3)
Attribute
Non-isolated, shared with analog inputs
Isolated