Rockwell Automation Publication 2080-UM002N-EN-E - November 2022
Chapter 4 Wire Your Controller
Use Surge Suppressors
Because of the potentially high current surges that occur when switching inductive load
devices, such as motor starters and solenoids, the use of some type of surge suppression to
protect and extend the operating life of the controllers output contacts is required. Switching
inductive loads without surge suppression can significantly
reduce the life expectancy of relay
contacts. By adding a suppression device directly across the coil of an inductive device, you
prolong the life of the output or relay contacts. You also reduce the effects of voltage
transients and electrical noise from radiating into adjacent systems.
shows an output with a suppression device. We recommend that you locate the
suppression device as close as possible to the load device.
Figure 3 - Output with Suppression Device
If the outputs are DC, we recommend that you use an 1N4004 diode for surge suppression, as
shown in
. For inductive DC load devices, a diode is suitable. A 1N4004 diode is
acceptable for most applications. A surge suppressor can also be used. See
. These surge suppression circuits connect directly across the
load device.
Figure 4 - DC Outputs with Surge Suppression
Suitable surge suppression methods for inductive AC load devices include a varistor, an RC
network, or an Allen-Bradley surge suppressor, shown in
. These components must be
appropriately rated to suppress the switching transient characteristic of the particular
inductive device. See
Recommended Surge Suppressors on page 45
for recommended
suppressors.
Wire Requirements
Wire Size
Type
Min
Max
Micro830/
Micro850/
Micro870
Controllers
Solid
0.2 mm
2
(24 AWG)
2.5 mm
2
(12 AWG)
rated @ 90 °C (194 °F)
insulation max
Stranded
0.2 mm
2
(24 AWG)
2.5 mm
2
(12 AWG)
+DC or L1
Suppression
device
DC COM or L2
AC or DC
outputs
Load
VAC/DC
Out 0
Out 1
Out 2
Out 3
Out 4
Out 5
Out 6
Out 7
COM
+24V DC
IN4004 diode
Relay or solid-
state DC outputs
24V DC common
VAC/DC
Out 0
Out 1
Out 2
Out 3
Out 4
Out 5
Out 6
Out 7
COM
A surge suppressor can
also be used.
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...