Appendix G Connect to Networks using DF1
Configure a Radio Modem
Station
To configure a Micro800 controller channel 1 for DF1 Radio Modem, do the following using your
programming software:
Table 97 - DF1 Half-Duplex Slave Communication Diagnostics Parameters
Status Field
Definition
Packets Sent
The total number of DF1 messages sent by the controller (including message
retries).
Packets Received
The number of messages received with no errors.
NAKs Received
The number of NAKs received by the controller.
No Memory for Receiving
The number of times the controller could not receive a message because it did not
have available memory.
Messages Retried
The number of message retries sent by the controller.
Undelivered Packets
The number of messages that were sent by the controller but not acknowledged by
the destination device.
Duplicate Received
The number of times the controller received a message packet identical to the
previous message packet.
Bad Packets Received
The number of incorrect data packets received by the controller for which no ACK
was returned.
2. See
for details concerning the DF1
Half-Duplex Slave Communication
Diagnostics screen.
1. To bring up the configuration page, click
Serial Port.
2. On the Serial Port configuration page, select
Radio Modem for your DF1 Mode.
3. Configure the rest of the communication
driver according to
.
Table 98 - Configure a Micro800 controller for DF1 Radio Modem communication
Parameter
Default
Selections
Baud Rate
19,200
Select a communication rate that all devices in your system support. Configure all devices in the system for
the same communication rate.
Parity
None
Parity provides additional message packet error detection. To implement even parity checking, choose Even.
To implement odd parity checking, choose Odd. To implement no parity checking, choose None.
Node Address
1
A node address identifies the controller on the DF1 half-duplex link. Each station on a link must have a unique
node address. Choose an address between 0
10
and 254
10.
Node address 255
10
is the broadcast address, which
you cannot select as a station’s individual address.
Enable Store and Forward
Not selected (Disabled)
See
Configure the Store and Forward Table on page 350
for more information.
Содержание 2080-L50E-24AWB
Страница 14: ...14 Rockwell Automation Publication 2080 UM002N EN E November 2022 Notes ...
Страница 54: ...54 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 4 Wire Your Controller Notes ...
Страница 128: ...128 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 7 Program Execution in Micro800 Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 8 EtherNet IP Network Notes ...
Страница 198: ...198 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 9 Motion Control Notes ...
Страница 232: ...232 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 11 Controller Security Notes ...
Страница 260: ...260 Rockwell Automation Publication 2080 UM002N EN E November 2022 Chapter 12 Using microSD Cards Notes ...
Страница 266: ...266 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix A Modbus Mapping for Micro800 Notes ...
Страница 275: ...Rockwell Automation Publication 2080 UM002N EN E November 2022 275 Appendix B Quickstarts 10 Click Finish to complete ...
Страница 332: ...332 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix E PID Function Blocks Notes ...
Страница 352: ...352 Rockwell Automation Publication 2080 UM002N EN E November 2022 Appendix G Connect to Networks using DF1 Notes ...
Страница 388: ...388 Rockwell Automation Publication 2080 UM002N EN E November 2022 Index Notes ...