Cat. No. 1771-ID16 Series B

Use this document as a guide when installing the ac Isolated Input
module.

    

$(" $%(#* %$

#&%(*$* )( $%(#* %$

$ * " $" $

"+"* &%,( ('+ (#$*)

* *  "*( * #

- * !&"$ %$$*%(

$)*"" * #%+" $  " , ( $ (#

%$$* * , ( $ *% * #%+"

$*(&(* * )**+)  $ *%()

.(%+) %* %$)

&  * %$)

This module must be used in a series B or later 1771 I/O chassis. The
1771-ID16 is not compatible with the 1771-AL local I/O adapter.

This module contains customer-selectable input filtering to limit the
effects of voltage transients caused by contact bounce and/or radiated
electrical noise. The delay due to filtering is 9.0 or 18.0ms for
turning ac inputs on to off, and 0.57ms for turning ac inputs off to
on: 9.0ms for turning dc inputs on to off, and 0.57ms for turning dc
inputs off to on. The filter time is factory set to 9.0ms.

The module is designed to operate with limit switches, float
switches, selector switches, and pushbutton switches.

Installation Instructions

 

   

Содержание 1771-ID16

Страница 1: ...tering to limit the effects of voltage transients caused by contact bounce and or radiated electrical noise The delay due to filtering is 9 0 or 18 0ms for turning ac inputs on to off and 0 57ms for turning ac inputs off to on 9 0ms for turning dc inputs on to off and 0 57ms for turning dc inputs off to on The filter time is factory set to 9 0ms The module is designed to operate with limit switche...

Страница 2: ...blication Allen Bradley publication SGI 1 1 Safety Guidelines for Application Installation and Maintenance of Solid State Control available from your local Rockwell Automation office describes some important differences between solid state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication Reproduction ...

Страница 3: ...uipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding speci...

Страница 4: ...ackplane from the chassis power supply The module requires 75mA from the output of this supply Add this to the requirements of all other modules in the I O chassis to prevent overloading the chassis backplane and or backplane power supply The input module has 2 customer selectable input filter time jumpers Jumper JPR 1 sets the input filter time for inputs 00 through 07 and jumper JPR 2 sets the i...

Страница 5: ...ion the jumpers as required to provide the filter time you require see below Use your fingers to pull the jumper up and position over the 2 pins corresponding to your selection Fast or Norm Setting the Filter Time Jumpers Jumper Position Time Constant ms Fast factory default 9 0 ac dc Norm 18 0 ac only 3 Reinstall the covers on the module circuit board and secure with 4 screws Table A Minimum and ...

Страница 6: ...aults ATTENTION 22 24 26 28 ATTENTION Remove power from the 1771 I O chassis backplane before you install the module Failure to remove power from the backplane could cause module damage degradation of performance injury or equipment damage due to possible unexpected operation WARNING When you insert or remove the module with field power applied or connect or disconnect the field wiring arm with fi...

Страница 7: ...the module to secure it 17643 wiring arm remove horizontal bar Attach the wiring arm 1771ĆWN to the horizontal bar at the bottom of the I O chassis The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires 1771ĆWN The 1771 ID16 B module is a modular component of the 1771 I O system requiring a properly installed system chassis...

Страница 8: ...ical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding ATTENTION Remove power from the 1771 I O chassis backplane and field wiring arm before removing or installing an I O module Failure to remove power from the backplane or wiring arm could cause module damage degradation of performance or in...

Страница 9: ...ac dc 120V Isolated Input Module 9 Figure 1 Connection Diagram for the 1771ĆID16 ac dc 120V Isolated Input Module ac Input dc Input ATTENTION Maintain isolation between phases to prevent module damage ...

Страница 10: ...ated Input Module Cat No 1771 ID16 L1 ac high 10559 I 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 AC 120V Isolated Output Module Cat No 1771 OD16 120V ac Supply L2 ac low AC DC 120V Isolated Input Module Cat No 1771 ID16 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 A O 1 2 3 4 5 6 7 B L2 ac low L1 ac high AC 120V Output...

Страница 11: ... consisting of 16 input status indicators and an active indicator The 16 status indicators will light when the field load has been applied to the field wiring arm of the module The active indicator will light when the module has successfully started up and has initialized ...

Страница 12: ...ns batteries they must only be changed in an area known to be nonhazardous Informations sur l utilisation de cet équipement en environnements dangereux Les produits marqués CL I DIV 2 GP A B C D ne conviennent que une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livré avec des marquages sur sa plaque d identification qui indique...

Страница 13: ... to 1500V ac channelĆtoĆchannel for 1s 1500V ac channel to backplane for 1s Maximum Cable Length 1000ft 304 8m Conductors Wire Size Category Only 14 to 22 gauge 2 5mm2 to 0 25mm2 stranded or solid copper rated at 60o or greater1 2 3 64 inch 1 2mm insulation maximum 13 Environmental Conditions Operating Temperature IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60...

Страница 14: ...ion 2 Group A B C D Hazardous Locations CE4 European Union 89 336 EEC EMC Directive compliant with EN 61000 6 4 Industrial Emissions EN 50082 2 Industrial Immunity EN 61326 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity European Union 73 23 EEC LVD Directive compliant with EN 61131 2 Programmable Controllers C Tick4 Australian Radiocommunications Act compliant with AS NZ...

Страница 15: ...ac dc 120V Isolated Input Module 15 ...

Страница 16: ...Publication 1771ĆIN070B EN P August 2002 Supersedes publication 1771Ć5 70 November 1999 PN957707 56 Copyright 2002 Rockwell Automation Inc Printed in USA ...