Radiated RF Immunity
IEC 61000-4-3
•
10V/m with 1 kHz
sine-wave 80% AM from
80…2000 MHz
•
10V/m with 200 Hz 50%
Pulse 100% AM at 900
MHz
•
10V/m with 200 Hz 50%
Pulse 100% AM at 1890
MHz
•
3V/m with 1 kHz
sine-wave 80% AM from
2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4
±4 kV at 5 kHz on
communication ports
Surge Transient Immunity
IEC 61000-4-5
±2 kV line-earth(CM) on
communication ports
Conducted RF Immunity
IEC 61000-4-6
10V rms with 1 kHz
sine-wave 80% AM from
150 kHz…80 MHz