The BonusPower is available when power comes on and after the end of an
output short circuit or output overload.
Hold-up Time
Figure 11 - Bonus Time Versus Output Power
Figure 12 - BonusPower Recovery Time
g
max
Bonus Time
0
100
120
130
140
150
170%
1
2
3
4
5 s
110
160
Output Power
min
Power
Demand
100%
t
t
Limitation by
Power Manager
Output
Voltage
Bonus Power disabled
Bonus
Time
Recovery Time
Figure 13 - BonusPower After Input Turn-on
Figure 14 - BonusPower After Output Short
100%
Output
Voltage
Input
Voltage
Bonus
Power
Output
Power
150%
Short of
Output
100%
Output
Voltage
Bonus
Power
Output
Power
150%
Attributes
Values
Notes
AC 100V
AC 120V
AC 230V
Hold-up Time
Typ
54 ms
54 ms
54 ms
At 48V, 10 A, see
Min
45 ms
45 ms
45 ms
Typ
27 ms
27 ms
27 ms
At 48V, 20 A, see
Min
23 ms
23 ms
23 ms
Figure 15 - Hold-up Time Versus Input Voltage
Figure 16 - Shutdown Behavior Definitions
0
10
20
30
40
60 ms
90
120
155
190
230V AC
Input Voltage
50
Hold-up Time
48V, 20 A, typ
48V, 10 A, min
48V, 10 A, typ
48V, 20 A, min
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage