1606-XLS120E Power Supply  Instruction Manual  

 

 

 

 

 

 

 

Technical Data 

 

 

 

 

 

 

 

1606-XLS120E 

 

 

 

Output Voltage 

 

DC 24-28V 

 

 

externally adjustable 

Factory Set 

typ. 

24.1V 

 

 

at full rated load 

Output Current 

min 

5-4.5A 

 

 

continuous 

 

min 

7.5-6.7A 

 

 

for typ. 4 sec 

Output Power 

min. 

120W 

 

 

continuous 

 

min. 

180W 

 

 

for typ. 4 sec 

Output Ripple 

max.  50mVpp 

 

 

BW DC to 20MHz 

Over-voltage Protection 

max.  36Vdc 

 

 

 

AC Input Voltage 

AC 100-240V 

-15/+10%

, 50-60Hz 

TN, TT and IT mains 

AC Input Current 

max.  1.4-0.65A 

 

 

at 100-240Vac 

DC Input 

 - 

DC 110-300V -20/+20% 

 

DC Input Current 

max.  1.2-0.45A 

 

 

at 110 - 300Vdc 

Power Factor 

typ. 

0.99-0.91 

at 100 - 230Vac 

AC Inrush Current 

max.  15A peak, 1A

2

s  

at 100 - 230Vac 

Efficiency 

typ. 

91.6 / 92.7% 

 

 

at 120 / 230Vac 

Losses 

typ. 

11.0 / 9.4W 

 

 

at 120 / 230Vac 

Hold-up Time 

typ. 

33 / 59ms 

 

 

at 120 / 230Vac 

Capacitive Loads 

 - 

no limitations 

 

Inductive Loads 

 - 

no limitations 

 

Limited Warranty 

 - 

1 year from date of purchase 

 

 

Environment 

 

 

 

Protection

 

Operational temperature 

-25 to +70°C 

De-rate above +60°C 

 

Output 

Overload, no-load, short-circuit proof 

Storage temperature 

-40 to +85° C 

Storage, transport 

 

Degree of protection 

IP 20 

EN/IEC 60529 

Humidity 

5 to 95% RH 

No condensation allowed 

 

Class of protection 

PE (Ground) connection required! 

Vibration sinusoidal 

2g 

IEC 60068-2-6 

 

Degree of pollution 

EN 50178, not conductive 

Shock 

15g 6ms, 10g 11ms 

IEC 60068-2-27 

 

Over-temperature protection 

yes 

Output shut-down with automatic restart 

 

Output over-voltage protection 

yes 

Output shut-down with automatic restart 

 

Over-voltage category 

III 

EN 50178 

Penetration protection 

>3.5mm 

e.g. screws, small parts … 

Internal input fuse 

T3.15A 

Device protection, not externally 
accessible 

Allowed output current versus 
the ambient temperature  
 

Ambient temperature is defined 
2cm below the unit.

 

0%

25%

50%

75%

100%

125%

150%

-40°C -20°C

0°C

20°C 40°C

60°C 80°C

Ambient Temperature

for ty p. 4s

continuous

 

 

External fuse on input 

Choose value according to the steady state input 
current, if needed for branch circuit protection. 

 

Functional Diagram 

 

Dielectric Strength 

 

Type tests and factory tests:

  

Conducted by the manufacturer.  
Do not repeat test in field!

 

Field test rules:

 

(1) Use appropriate test equipment which 
     apply the voltage with a slow ramp!  
(2) Connect L and N together as well as all  
     output poles. 
(3) Use only AC test-voltages with 50/60Hz. 
The output voltage is floating and has no ohmic 
reference to ground. 

A

D

C

B

B

N

L

Input

DC-ok

Earth

Output

 -

+

 

 

Type Test

 

60s 

2500Vac 

3000Vac 

500Vac 

500Vac 

 

Factory Test

 

5s 

2500Vac 

2500Vac 

500Vac 

500Vac 

+

+

-
-

V

OUT

DC
ok

Output

Over-

Voltage

Protection

PFC

Converter

Input Fuse
Input Filter
Input Rectifier
Inrush Limiter
Transient Filter

Output

Voltage

Regulator

Power

Converter

Output

Filter

DC ok

Relay

Output

Voltage
Monitor

Output

Power

Manager

Temper-

ature

Shut-

down

Over-

load

DC

ok

L

N

 

 

 

Field Test

 

5s 

2000Vac 

2000Vac 

500Vac 

500Vac 

 

 

 

Overload Behaviour 

The unit is designed to support loads with a higher short-term 
power requirement without damage or shutdown. 

0V

4V

8V

12V

16V

20V

24V

28V

0A

2A

4A

6A

8A 10A 12A

continuous

for 4s

Output Current

 

0s

2s

4s

6s

8s

10s

110% 120% 130% 140% 150% 160%

Output Current

min.

max.

 

Output characteristic 

(typ.) 

Curve is valid for the 24V unit. Units with 
output voltages other than 24V have an 
equivalent and proportional behaviour. 

Bonus time

 

Duration until the output starts dipping. Bonus 
Time is hardware controlled. 

Repetitive pulse loading:

 Multiple pulses can be supported as long as the average (R.M.S.) 

output current stays below the specified continuous output current. If it is higher, the unit will 
respond with a thermal shut-down. 

Examples for pulse load 
compatibility: 

P

PEAK

 

P

0

 

T

PEAK

 

T

0

 

180W 

120W 

1s 

>25s 

180W 

0W 

1s 

>1.3s 

180W 

60W 

0.1s 

>0.16s 

180W 

60W 

1s 

>1.6s 

DC-ok Relay Contact  

This feature monitors the output voltage, which is produced by the power supply, and is 
independent of a return voltage from a unit which is connected in parallel. 

Contact closes

   as soon as the output voltage reaches the nominal value. 

Contact opens

   as soon as the output voltage dips more than 10%.  

                            Short dips will be extended to a length of 250ms on the relay.  
                            Dips shorter than 1ms will be ignored. 

Contact ratings

  60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load 

250ms

90%

V

ADJ

V

ADJ

closed

open

> 1ms

< 1ms

10%

open

closed

V

OUT

 

 

Please note:

 

The DC-ok feature requires that the output voltage reach the nominal (=adjusted) level after 
turn-on in order to function to specification. If this level cannot be achieved, the unit will show 
an overload condition. The overload signal will disappear as soon as the adjusted voltage is 
reached. This is an important to condition to consider particularly, if the load is a battery or 
the power supply is used for N+1 redundant systems. 

 

t

100%

P

PEAK

0%

T

PEAK

P

0

T

0

P

OUT

max.

150%

t

 

180W 

60W 

3s 

>4.9s 