Rockwell Automation 1606-XLE Скачать руководство пользователя страница 3

1606-XLE-Series Power Supply Instruction Manual 

 

 

 

 

   

 

 

 

Technical Data 

1)

 Technische 

Daten 

1)

 

 

1606-
XLE80E 

1606-XLE 
120E 
1606-XLE 
120EC 

2)

 

1606-
XLE120EN

1606-
XLE120EE

1606-  
XLE240E 

1606-    
XLE240EP 

1606-
XLE240EN

1606-
XLE240EE

1606-
XLE240F 

Output Voltage 

Ausgangsspannung 

nom. 

24 - 28V 

24 - 28V 

24 - 28V 

24 - 28V 

24 - 28V 

24 - 28V 

24 – 28V 

24 - 28V 

48 - 52V 

Factory Setting 

Werkseinstellung 

typ. 

24.1V 24.1V 24.1V 24.1V 24.1V 24.1V 24.1V 24.1V 48.0V 

Output Current 

Ausgangsstrom

 

nom. 

3.3 - 2.7A 

5 - 4.3A 

5 - 4.3A 

5 - 4.3A 

10 - 8.6A 

10 - 8.6A 

10 - 8.6A 

10 - 8.6A 

5 - 4.6A 

 

 

Power Boost 

N/A 

14)

 

6 - 5.1A 

3) 4)

 

6 - 5.1A 

3) 4)

 

6 - 5.1A 

3)

 

12 - 10.3A 

3)

  12 - 10.3 

5)

 

12 - 10.3A 

3)

  12 - 10.3A 

3)

  6 - 5.5A 

3)

 

Output Power 

Ausgangsleistung

 

nom. 

80W  120W 120W 120W 240W 240W 240W 240W 240W 

 

 

Power Boost 

N/A 

14)

 144W 

3) 4)

 144W 

3) 4)

 144W 

3)

 288W 

3)

 288W 

5)

 288W 

3)

 288W 

3)

 288W 

3)

 

Output Ripple 

19)

 Ausgangswelligkeit 

19)

 

max. 

50mVpp 50mVpp 50mVpp 50mVpp 50mVpp 50mVpp 50mVpp 50mVpp 100mVpp 

AC Input Voltage 

AC Eingangsspannung 

nom. 

100-240Vac 

±10%

 

100-120Vac/ 
200-240Vac 

±10%

 

100-120Vac 

±10%

 

200-240Vac 

±10%

 

100-120Vac/ 
200-240Vac 

±10%

 

100-120Vac/ 
200-240Vac 

±10%

 

100-120Vac 

±10%

 

200-240Vac 

±10%

 

100-120Vac/ 
200-240Vac 

±10%

 

 

 

 

Wide-Range 

Auto-Select 

-- -- Auto-Select 

Auto-Select 

-- -- Auto-Select 

AC Input Current 

16)

 AC 

Eingangsstrom 

16)

 

typ. 

1.4 / 0.75 

2.6 / 1.4A 

2.6A / -- 

-- / 1.4A 

5.0 / 2.7A 

5.0 / 2.4A 

5.0A / -- 

-- / 2.7A 

5.0 / 2.7A 

DC Input Voltage 

7)

 DC 

Eingangsspannung 

7)

 

88 - 375Vdc  N/A 

14)

 N/A 

14)

 210 

375Vdc N/A 

14)

 N/A 

14)

 N/A 

14)

 210 

375Vdc N/A 

14)

 

Power Factor 

17)

 Leistungsfaktor 

17)

 

typ. 

0.61 / 0.56 

0.56 / 0.47 

0.59 / -- 

-- / 0.5 

0.59 / 0.51 

0.59 / 0.57 

0.57 / -- 

-- / 0.52 

0.59 / 0.51 

Harmonic Correction 

18)

 Oberwellenkorrektur 

18)

 

 

No / Nein 

No / Nein 

No / Nein 

No / Nein 

No / Nein 

Yes / Ja 

No / Nein 

No / Nein 

No / Nein 

EN 61000-3-2 

EN 61000-3-2 

 

Yes / Ja 

No / Nein 

N/A 

14)

 

Yes / Ja 

No / Nein 

Yes / Ja 

N/A 

14)

 

No / Nein 

No / Nein 

Input Inrush Current 

11)

 Einschaltspitzenstrom

11)

120Vac, typ. 

23A; 0.5A

2

s 3A; 

1A

2

s 45A; 

3A

2

s -- 

3A; 

1A

2

s 3A; 

1A

2

s 85A; 

8,5A

2

s -- 

3A; 

1A

2

s  

 

 

230Vac, typ. 

45A; 1.7A

2

s 3A; 

1A

2

s -- 

30A; 

1A

2

s 3A; 

1A

2

s 3A; 

1A

2

s -- 

48A; 

3A

2

s 3A; 

1A

2

s  

Efficiency 

17)

 Wirkungsgrad 

17)

 

typ. 

88,0/89,8% 

89,4/90,2% 

90,0% / -- 

-- / 90,2% 

91,0/91,6% 

91,0/91,6% 

90,8% / -- 

-- / 91,6% 

91,4/92,0% 

Power Losses 

17)

 Verlustleistung 

17)

 

typ. 

11,1/9,1W 

14,5/13,2W 

13,5W / -- 

-- / 13,2W 

24,1/22,4W 

24,1/24,1W 

24,0W / -- 

-- / 22,7W 

22,6/20,9W 

Hold-up Time 

17)

 Pufferzeit 

17)

 

typ. 

29 / 120ms 

80 / 78ms 

80ms / -- 

-- / 78ms 

46 / 47ms 

46 / 42ms 

46ms / -- 

-- / 45ms 

46 / 47ms 

Operational Temperature  Betriebstemperatur 

 

-25 - +70°C 

-25 - +70°C 

-10 - +70°C 

-10 - +70°C 

-25 - +70°C 

-25 - +70°C 

-10 - +70°C 

-10 - +70°C 

-25 - +70°C 

Output Derating 

Leistungsrücknahme 

+60 - +70°C 

1.8W/°C 

3W/°C 3W/°C 3W/°C 6W/°C 6W/°C 6W/°C 6W/°C 6W/°C 

Storage Temp. Range 

Lagertemperaturbereich 

 

-40 - +85°C 

-40 - +85°C 

-40 - +85°C 

-40 - +85°C 

-40 - +85°C 

-40 - +85°C 

-40 - +85°C 

-40 - +85°C 

-40 - +85°C 

Humidity 

20)

 Feuchte 

20)

 

IEC60068-2-30 

5 - 95% r.H. 

5 - 95% r.H. 

5 - 95% r.H. 

5 - 95% r.H. 

5 - 95% r.H. 

5 - 95% r.H. 

5 - 95% r.H. 

5 - 95% r.H. 

5 - 95% r.H. 

Vibration Schwingen 

IEC 60068-2-6 

2g 2g 2g 2g 2g 2g 2g 2g 2g 

Shock Schocken 

IEC60068-2-27  30g 6ms 

30g 6ms 

30g 6ms 

30g 6ms 

30g 6ms 

30g 6ms 

30g 6ms 

30g 6ms 

30g 6ms 

Degree of Pollution 

Verschmutzungsgrad 

EN 50078 

2 2 2 2 2 2 2 2 2 

Degree of Protection 

Schutzart 

EN 60529 

IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 

Class of Protection 

Schutzklasse 

IEC 61140 

6)

 I 

6)

 I 

6)

 I 

6)

 I 

6)

 I 

6)

 I 

6)

 I 

6)

 I 

6)

 

Over-temp. Protection 

15)

 Übertemperaturschutz

15)

 

No / Nein 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Over-voltage Protection

15)

 Überspannungsschutz

15)

typ. 

34Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 56Vdc 

Return Voltages 

8)

 Rückspeisefestigkeit 

8)

 

max. 

35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 63Vdc 

Parallel Use 

12)

 Parallelschaltbar 

13)

 

 

No / Nein 

No / Nein 

No / Nein 

No / Nein 

No / Nein 

No / Nein 

No / Nein 

No / Nein 

No / Nein 

Serial Use 

13)

 Serienschaltbar 

14)

 

 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Yes / Ja 

Dimensions 

9)

 

(wxhxd)

 Abmessungen 

9)

 

(BxHxT)

nom. 

32x124x102 32x124x117 32x124x117 32x124x117 60x124x117 60x124x117 60x124x117 60x124x117 60x124x117 

Weight Gewicht 

max. 

430g / 0.95lb 500g / 1.1lb 

500g / 1.1lb 

500g / 1.1lb 

700g / 1.54lb 800g / 1.76lb  700g / 1.54lb 700g / 1.54lb 700g / 1.54lb

Approvals Zulassungen 

 

 

10)

  

 

10)

  

 

10)

  

 

10)

  

 

10)

  

 

10)

  

 

10)

  

 

10)

  

 

10)

  

Limited Warranty 

(Year)

 Gewährleistung 

 

(Jahre)

 

 

1 1 1 1 1 1 1 1 1 

1) 

All parameters are specified at 230Vac input voltage, nominal output current, 25°C ambient and after a 5 
minutes run-in time unless otherwise noted. 

2) 

The model 1606-XLE120EC are identical to the model 1606-XLE120E with the exception that the PC board 
is conformal coated. 

3) 

The PowerBoost is continuously allowed up to an ambient of 45°C. Above that temperature, do not use the 
PowerBoost longer than a duty cycle of 10% and not longer than 1 minute every 10 minutes. 

4) 

The unit can respond with a thermal shut-down when continuously loaded with more than 120W and 
operated with a mains voltage of 100V or below. 

5) 

Do not use the PowerBoost longer than a duty cycle of 10% and not max. 1 minute every 10 minutes. 

6) 

PE connection required (Ground). 

7) 

Use a battery or similar DC source. Cpole to L and -pole to N. 

8) 

Loads such as decelerating motors and inductors can feed voltage back to the output of the power supply. 
The figure represents the maximum allowed feed-back voltage 

9) 

Dimensions in mm. Depth without DIN-rail. 

10) 

See datasheet or markings on the unit. 

11) 

Peak value and inrush energy at an ambient temperature of 40°C and cold start. 

12) 

The power supplies shall not be used in parallel in order to increase the output power. However, units can 
be paralleled for building 1+1 redundancy systems or to deliver short-term peak currents to the load when 
the average current is smaller than the current of one power supply. 

13) 

Use only power supplies of the same type. The total output voltage should not exceed 150Vdc. 

14) 

Not applicable 

15) 

Output shut-down with automatic restart 

16) 

At full load and the lower end of the input voltage of 120/230Vac 

17) 

At full load and nominal input voltage of 120/230Vac 

18) 

Harmonic correction describes whether the input current waveform is filtered in order to reduce the amount 
of harmonic current. A not filtered unit does not necessarily mean that the EN 61000-3-2 is not fulfilled. 

19) 

50 Ohm measurement, bandwidth 20MHz  

20) 

Do not energize while condensation is present. 

 

1) 

Alle Werte gelten bei 230Vac Eingangsspannung, Nennausgangsstrom, 25°C Umgebung und nach 
einer Aufwärmzeit von 5 Minuten, wenn nichts anderes angegeben ist. 

2) 

Das Model 1606-XLE120EC ist identisch zum Model 1606-XLE120E mit der Ausnahme, dass die 
Leiterplatten mit Schutzlack überzeugen sind. 

3) 

Der PowerBoost kann <45°C dauerhaft entnommen werden. Über 45°C ist eine max. Einschaltdauer 
von 10% erlaubt, die nicht öfters als 1 Minute alle 10 Minuten wiederholt werden darf. 

4) 

Bei einer Dauerbelastung >120W und einer Eingangsspannung <120Vac kann das Gerät thermisch 
abschalten. 

5) 

Der PowerBoost darf mit einer max. Einschaltdauer von 10% und nicht öfters als 1 Minute alle 10 
Minuten entnommen werden. 

6) 

PE Verbindung erforderlich. 

7) 

Geeignet sind Batterien oder ähnliche Quellen. Den + Pol an L und - Pol an N anschließen. 

8) 

Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils rückspeisen. 
Der Wert gibt die max. zulässige Rückspeisespannung an. 

9) 

Abmessungen in mm. Tiefe ohne DIN-Schiene 

10) 

Siehe Datenblatt oder Prüfzeichen auf dem Gerät. 

11) 

Spitzenwert und Einschaltenergie bei einer Umgebungstemperatur von 40°C und Kaltstart 

12) 

Ausgänge der Stromversorgung sollen nicht parallel geschaltet werden. Eins Parallelschaltung ist nur 
für 1+1 Redundanzanwendungen oder zur Abdeckung kurzer Spitzenlasten erlaubt, wenn der mittlere 
Ausgangsstrom kleiner ist als der Nennstrom eines Gerätes 

13) 

Nur gleiche Geräte bis zu einer Gesamtspannung von 150Vdc 

14) 

Nicht anwendbar 

15) 

Ausgang schaltet ab und macht regelmäßig automatische Startversuche 

16) 

Bei Nennlast und dem unteren Ende der Eingangsspannung von 120/230Vac 

17) 

Bei Nennlast und Nenneingangsspannung von 120/230Vac 

18) 

Die Angabe Oberwellenkorrektur gibt an ob die Kurvenform des Eingangsstromes gefiltert ist. Ein 
nicht gefiltertes Gerät kann aber trotzdem die Anforderungen der EN 61000-3-2 erfüllen. 

19) 

50 Ohm Messung, Bandbreite 20MHz 

20) 

Nicht betreiben, solange das Gerät Kondensation aufweist. 

 

EMC  Electromagnetic Compatibility

 

These devices are suitable for applications in industrial environment as well as in residential, 
commercial and light industry environment. Please note that for some units restrictions may apply 
since the EN 61000-3-2 requirements are not fulfilled on all units. See also datasheet for details. 
These devices comply with FCC Part 15 rules. Operation is subjected to following two conditions: (1) 
this device may not cause harmful interference, and (2) this device must accept any interference 
received, including interference that may cause undesired operation.  
CE mark is in conformance with EMC directive 89/336/EC, 93/68/EC and 2004/108/EC and the low-
voltage directive (LVD) 73/23/EC, 93/68/EC, 2006/95/EC. 

EMC Immunity: 

EN 61000-6-1, EN 61000-6-2

 

EMC Emission:

 For all units: EN 61000-3-3, EN 61000-6-4, FCC Part 15 Class B 

 

EN 61000-6-3, EN 61000-3-2: For units which are marked with “Yes” in the row EN 
61000-3-2 of the technical data table. 

 

EMV  Elektromagnetische Verträglichkeit

 

Diese Geräte erfüllen die Anforderungen für Anwendungen sowohl in industrieller Umgebung 
als auch für den Wohn-, Geschäfts- und Gewerbebereich.  
Einige dieser Gerätetypen erfüllen die Anforderungen der EN 61000-3-2 nicht und es kann 
daher zu Einschränkungen bei Anwendungen kommen. Siehe auch Details im Datenblatt. 
Die Geräte erfüllen auch die Anforderungen der FCC Teil 15.  
Das CE Zeichen ist angebracht und erklärt die Erfüllung der EMV Richtlinien 89/336/EG, 
93/68/EG, 2004/108/EG und der Niederspannungsrichtlinie 73/23/EG, 93/68/EG, 2006/95/EG. 

EMV Störfestigkeit:  

EN 61000-6-1, EN 61000-6-2 

EMV Störaussendung:

   Für alle Geräte: EN 61000-3-3, EN 61000-6-4, FCC Part 15 Klasse B

EN 61000-3-2, EN 61000-6-3: Für Geräte die in der Spalte EN 
61000-3-2 der Tabelle mit den technischen Daten den Eintrag „Ja“ 
haben. 

 
 

Отзывы: