Ed. 11/2006
User, Installation and Service Manual for F1 Gas Unit Heaters
6
TECHNICAL CHARACTERISTICS
MODEL
UNIT
F1 21
F1 31
F1 41
F1 51
F1 61
F1 81
Appliance Category
II
2H3+
Appliance type
C
13
- C
33
- B
23 -
C
63
- C
53
Nominal heat input
(5)
kW 23,08
30,77 37,15 48,35 61,32 77,14
BTU 78804 105046
126841 165072 209357 263369
Nominal heat output
kW
21
28
33,8
44
55,8
70,2
BTU
71698
95597
115407 150224 190520
239668
Efficiency
(5)
%
91
91 91 91 91 91
Nominal air flow
(1)
m
3
/h
2000
2700 3400 4200 5200 7800
Temperature rate
K
31,1
30,7
29,5
31
31,8
26,7
Gas Consumption
(2)
Natural
Gas m
3
/h
2,43
3,25 3,93 5,11 6,49 8,16
LPG
G30
LPG
G31
kg/h
kg/h
1,80
1,78
2,42
2,38
2,93
2,87
3,81
3,74
4,84
4,75
6,09
5,97
Inlet gas pressure
Natural Gas
LPG.
G30
LPG
G31
mbar
20
30
37
Diameter gas inlet
"
3/4F
Pipe Diameter
air
mm
80
flue
mm
80
Voltage
230V - 50Hz
Wattage W
260
400
450
640
900
Operating temperature
°C
0° +35°
(4)
Fuse A
6,3
Throw
(residual air speed >1m/s)
(3)
m
14
16 20 22 25 29
Noise level 6 m distance
in free field
dB(A)
41
43
44
46
47
49
in tipycal installation
dB(A)
53
55
56
57
60
63
Weight kg
55
59
68
80
90
108
Table 1
1
At 20°C - 1013mbar
2
At 15°C - 1013mbar
3
THROWS FOR GUIDANCE ONLY. THROW DEPENDS ON HEIGHT OF THE BUILDING, MOUNTING HEIGHT OF THE HEATER, ROOM TEMPERATURE AND LOUVRE
SETTING.
4
WARNING: THE ROOM OPERATIONAL TEMPERATURE IS BETWEEN 0° AND +35°C ;THE APPLIANCE’S COMPONENTS OPERATIONAL TEMPERATURE IS BETWEEN
0° AND +60°C
5
DATA REFERED TO THE LOW HEAT VALUE (9,45 kWh/m
3
- 15°C 1013 mbar)
WITH THE AIM OF CONTINUOUSLY IMPROVING THE QUALITY OF ITS PRODUCTS, THE
MANUFACTURER RESERVES THE RIGHT TO VARY ABOVE INFORMATION WITHOUT ANY PRIOR
NOTICE.