Electrical installer
Installation, use and maintenance manual – AY
27
4
Table 4.1
CAN bus cables type
Cable name
Signals / Color
Maximum length
Note
Robur
Optional code OCVO008
ROBUR NETBUS
H = BLACK
L = WHITE
GND = BROWN
450 m
Honeywell SDS 1620
In all cases the fourth conductor should
not be used
BELDEN 3086A
H = BLACK
L = WHITE
GND = BROWN
450 m
TURCK type 530
DeviceNet Mid Cable
TURCK type 5711
H = BLUE
L = WHITE
GND = BLACK
450 m
Honeywell SDS 2022
TURCK type 531
H = BLACK
L = WHITE
GND = BROWN
200 m
How to connect the CAN bus cable to the appli-
ance
To connect the CAN bus cable to the CAN-NDG
electronic board, located at the rear of the electri-
cal panel inside the appliance:
1. Access the electrical board of the appliance ac-
cording to the Procedure 4.2
2. Turn the control panel 90° outwards, using the
side latches, to access the CAN-NDG board (Figure
4.4
p. 27).
3. Connect the CAN bus cable to terminals 0, L and H.
4. Place the CLOSED J11 jumpers (Detail A) if the node
is terminal (one connected CAN bus cable section
only), or OPEN (Detail B) if the node is intermediate
(two connected CAN bus cable sections).
5. Connect the DDC to the CAN bus cable according
to the instructions in the following Paragraphs and
in the DDC manual.
For the AY 100 appliance, the CAN bus connection
between the two modules is factory wired.
Figure 4.4
Access to CAN-NDG board
A CAN-NDG board
B
CAN bus port
A
B
Figure 4.5
Connection of the CAN bus cable to the electronic
board
C
Back of the electrical panel
D CAN-NDG board
E
Jumper J11
F
CAN bus port
C D
F
E
4.4.4
AY + DDC configuration
System (1) see also Paragraph 1.5