ROBUA QAC34/101 Скачать руководство пользователя страница 37

Settings 

Installation manual – System controller 

37

5

temperature acquired by the sensor, but a value which 

has passed an inertial filter. This accounts for the ther-

mal inertia of the building, thus damping the variation of 

the outlet setpoint in relation to changes in the outdoor 

temperature.

The filter is preconfigured to a value of 10 hours, which is 

suitable for a vast range of buildings with moderate ther-

mal inertia.

To modify this setting, proceed as follows:

1.  If needed, follow instructions in Paragraph 4.1.1 p. 28 

to access the complete parameter list, then access 

Configuration menu.

2.  Display and access the page containing parameter 

6110 (Time constant building), select it and set it to 

desired value:

 

„

0 h 

 Filter disabled (not recommended)

 

„

< 10 h 

 Building with low thermal inertia

 

„

10-20 h   Building with average thermal inertia

 

„

> 20 h 

 Building with high thermal inertia

5.1.7 

   Choice of installation and use of room 

units

The system is supplied with a QAA74.611 room unit. The 

room unit is preconfigured as Room unit 1 to acquire the 

room temperature in a reference heated room served by 

heating circuit 1, and to influence the regulation of this 

circuit accordingly and, if present, also that of heating 

circuit 2 (as described in Paragraph 5.1.5  p.  36). This 

setting is suited to the following type of installation:

 

Case 1

 

The included room unit is actually installed in a refer-

ence heated room.

 

Heating circuit 2 is not present or, if so, no dedicated 

room unit will be installed.

 

If both heating circuits are present: the reference 

room, served by heating circuit 1, is at least partly also 

representative of the rooms served by circuit 2.

You can adjust the parameters described in 

Paragraph 5.1.5 

p.  36, differentiating the settings 

for the two circuits, to the point even of disabling 

one or both of the room unit influence functions 

for heating circuit 2, which does not directly serve 

the reference room.

If, on the other hand, the situation is as follows:

 

Case 2

 

The included room unit is not installed in a reference 

heated room, for example, it is in the machine room.

In this case, you must configure the room unit so as not 

to provide the room temperature value to the system. 

Proceed as follows:

1.  If needed, follow instructions in Paragraph 4.1.1 p. 28 

to access the complete parameter list, then access 

Operator unit menu.

2.  Display and access the page containing parameter 40 

(Used as), select it and set it to Operator unit 1.

3.  Access Configuration menu.

4.  Display and access the page containing parameter 

6200 (Save sensors), select it and set it to Yes.

The value of parameter 6200 which displays at the 

end of the configuration procedure will still be no

this is normal (this setting executes an action, i.e. 

memorization of the actually installed sensors).

Finally, in the following situation:

 

Case 3

 

Both heating circuits are present.

 

A second room unit dedicated to heating circuit 2 is 

present.

In this case, you must configure the first room unit, in-

stalled in a reference room served by circuit 1, so that it is 

dedicated to that circuit. Proceed as follows, working on 

the first room unit:

1.  If needed, follow instructions in Paragraph 4.1.1 p. 28 

to access the complete parameter list, then access 

Operator unit menu.

2.  Display and access the page containing parameter 40 

(Used as), select it and set it to Room unit 1.

3.  Display and access the page containing parameter 

47 (Room values device 1), select it and set it to For 

zone 1 only.

4.  Display and access the page containing parameter 48 

(Warmer/cooler device 1), select it and set it to For 

zone 1 only.

You must now configure the second room unit, installed 

in a reference room served by heating circuit 2. Proceed as 

follows, depending on the type of room unit:

Second room unit type QAA74.611

Proceed as follows, working on the second room 

unit:

 

„

If needed, follow instructions in Paragraph 

4.1.1 

p. 28 to access the complete parameter list, 

then access Operator unit menu.

 

„

Display and access the page containing parameter 

40 (Used as), select it and set it to Room unit 2.

Second room unit type QAA55.110

Proceed as follows, working on the second room 

unit:

 

„

Press the occupancy button 

 for at least 3 

seconds, until the display reads ru = 1, ru = 2 or ru 

= 3.

 

„

Turn the knob to set the parameter to ru = 2.

 

„

Wait for the text ru = 2 to clear from the display.

Now, on the first room unit, proceed as follows:

5.  If needed, follow instructions in Paragraph 4.1.1 p. 28 

to access the complete parameter list, then access 

Configuration menu.

6.  Display and access the page containing parameter 

6200 (Save sensors), select it and set it to Yes.

The value of parameter 6200 which displays at the 

end of the configuration procedure will still be no

this is normal (this setting executes an action, i.e. 

memorization of the actually installed sensors).

Содержание QAC34/101

Страница 1: ...Installation manual System controller for modulating gas absorption condensing heat pump renewable aerothermal energy K18...

Страница 2: ...ained within this publication are not affected With the aim of continuously improving the quality of its products Robur S p A reserves the right to modify the data and contents of this Installation ma...

Страница 3: ...2 Temperature probes connection p 21 3 3 Water circulation pump connection p 22 3 4 Mixer diverter valve connection p 23 3 5 External requests connection p 25 3 6 K18 unit connection to CSK18 enclosu...

Страница 4: ...oiler equipment e g boiler for the produc tion of heat for space heating and or DHW able to inte grate or replace the heat pump of the K18 unit It is always found in the K18 Hybrigas type of unit and...

Страница 5: ...ins the Siemens RVS21 826 electronic board the relays and electrical terminal blocks 1 QAA74 611 advanced room unit 1 Siemens QAC34 outdoor temperature probe Optional additional room units are availab...

Страница 6: ...1 2 p 7 1 4 p 8 e 1 5 p 8 water circulation must be guaranteed to handle the K18 unit s antifreeze cycle In the diagrams given in Figure 1 2 p 7 and 1 5 p 8 this requires that a outlet inlet bypass is...

Страница 7: ...8 HC1 E G F Q2 HC2 G Q6 GHP A D K18 CONTROL CABLE AUX BOILER 230V W PUMP 0 10V W PUMP Figure 1 3 System with K18 Simplygas unit primary and secondary water circuits up to two heating circuits one of w...

Страница 8: ...Room unit 1 QAA74 611 P A ST B9 B3 Q3 F ST CSK18 HC1 GHP K18 CONTROL CABLE Figure 1 5 System with K18 Hybrigas unit primary water circuit only and two zones DHW production optional A K18 Hybrigas uni...

Страница 9: ...le cable glands not included to maintain the indicated protection rating if necessary Before installing the unit check that the equip ment is not connected to its power supply The cabling must satisfy...

Страница 10: ...ER ENCLOSURE 2 1 1 Mounting and installation Figure 2 1 External overall dimensions for CSK18 enclosure A Input of connections to the mains B Input of safety extra low voltage SELV connections C Do no...

Страница 11: ...uded extractable connec tors which fit directly onto the board Table 2 1 p 12 lists the Line Voltage supply and signal connections on the extractable connectors at the left edge of the Siemens RVS21 8...

Страница 12: ...N Not used 1 Not normally used It may be used In place of Q3 see Table 2 2 p 12 if the DHW diverter valve is set to DHW when the phase is NOT present at the output In addition to Q3 if the valve has...

Страница 13: ...H1 H3 2 Input H3 is open to keep heating circuit 2 inactive If this heating circuit is present fit a jumper between terminals H3 and H1 H3 or insert an external request signal between them voltage fre...

Страница 14: ...Mounting and installation Figure 2 3 Description of installation procedure for QAC34 external sensor H H 2 1 N N W 3 min2 5 m 1 2 4 Figure 2 4 QAC34 external room sensor dimensions 49 7 91 6 79 8 3 8...

Страница 15: ...rature as accurately as possible it should therefore be out of the way of draughts sunlight and other sources of heat If wall mounted leave enough space above the unit for it to be installed and remov...

Страница 16: ...Figure 2 7 Description of mounting holes for room unit QAA55 110 96 96 91 47 1 2 4 2 56 60 56 60 2 3 4 Electrical hookup Figure 2 8 Room unit QAA55 110 connections 1 3 4 5 6 2 Table 2 6 Room unit QAA5...

Страница 17: ...s accurately as possible it should therefore be out of the way of draughts sunlight and other sources of heat If wall mounted leave enough space above the unit for it to be installed and removed when...

Страница 18: ...8 86 48 96 2 4 4 Electrical hookup Figure 2 12 Room unit QAA74 611 connections Table 2 7 Room unit QAA74 611 connections Terminal Name Description 3 BSB Data bus BSB 2 M Data bus BSB 1 G Power 12 V D...

Страница 19: ...raph 3 7 p 27 4 GHP temperature sensor connection see Paragraph 3 7 p 27 5 Connection of 0 10 V signal on the optional external water pump only for K18 Simplygas C0 models see manual of specific K18 u...

Страница 20: ...Room unit 1 QAA74 611 C Ambient unit 2 QAA55 110 optional code ODSP004 NOTE Use shielded signal cable 3x0 75 mm2 2x0 75 mm2 for QAA55 110 Maximum total length 400 m Maximum length between controller...

Страница 21: ...ight edge of RVS21 826 board B1 NTC 10k Beta 3977 temperature sensor B3 NTC 10k Beta 3977 temperature sensor B9 NTC 1k temperatrue sensor included Use of temperature sensors B9 always B1 only if heati...

Страница 22: ...2 Heating circuit 1 pump KC1 Relay not supplied X15 1 QX4 QX4 N QX5 ZX6 N N A M Q2 X15 1 QX4 QX4 N QX5 ZX6 N N A M Q2 N L KC1 3 3 2 Heating circuit 2 pump connection diagram if any Figure 3 4 Direct o...

Страница 23: ...iverter valve CASE 1 Valve with power always present position controlled by signal 230VAC phase no phase heating phase DHW L L CTRL N N LINE IN DHW Q3 N F E B C D Q3 A Figure 3 6 Q3 diverter valve con...

Страница 24: ...l Q3 Diverter valve CASE 3 Valve with two signals 230VAC phase alternatively active for DHW and heating L L CTRL N N LINE IN DHW Q3 N F E B C D Q3 A X15 1 QX4 QX4 N QX5 ZX6 N N G 3 4 2 Y1 Y2 mixer val...

Страница 25: ...of optional external request signals thermostats thermostat timers timers to RVS21 826 A Grey connector X86 bottom edge of RVS21 826 board B NO voltage free contact must be SELV C1 Thermostat with ti...

Страница 26: ...ailable as OCVO009 optional Maximum length 50 m NOTE Connect the shield to the ground terminals at both ends Using DIN 47100 conforming cable colour coded simplifies the hookup see Table 3 2 p 26 AL A...

Страница 27: ...ce managed by the K18 unit is present Use shielded cable 2x0 5 mm2 up to 40 m 2x0 75 mm2 up to 60 m 2x1 0 mm2 up to 80 m 2x1 5 mm2 up to 120 m Connect the shield to a ground terminal on the K18 unit s...

Страница 28: ...ew seconds the device will automatically move to the start page Sometimes also i e immediately after powering up the system the display may show the message Operator unit being refreshed together with...

Страница 29: ...which contains the parameters of a specific menu Time of day and date Operator unit Configuration etc In the following part of the Installation manual when you are asked to check or change the value...

Страница 30: ...VO and in the case of the K18 Simplygas model there is also the auxiliary boiler select pa rameter 209 and set it to 1 5 Only if the unit is a K18 Simplygas model and the auxil iary boiler is present...

Страница 31: ...thermostat or a chronothermostat Display the page containing parameter 7844 Input signal H1 and by activating the external request check the correct switching between the Open state to Closed state an...

Страница 32: ...es to all units type K18 Hybrigas as well as to those type K18 Simplygas if an auxiliary boiler is present 1 On the K18 unit s user interface proceed as follows with reference to its Installation user...

Страница 33: ...select parameter 1000 Operating mode and set it to Protection 4 If DHW service is present access next the Domestic hot water menu select parameter 1600 Operating mode and set it to Off 5 Follow the in...

Страница 34: ...access the complete parameter list then access Heating circuit 2 menu then scroll through the pages to view the parameters shown in Table 5 2 p 34 and eventually ac cess the pages to be able to select...

Страница 35: ...nstaller and the flooring vendor for advice especially for parquet floors Moreover for floor heating systems it is recommended that the heating be supplied by a mixed heating circuit Furthermore excep...

Страница 36: ...s suited to many installations To modify the degree of influence or dis able the function for heating circuit 1 proceed as described in Paragraph 5 1 1 p 33 to edit parameter 750 Room influence for he...

Страница 37: ...e parameter list then access Operator unit menu 2 Display and access the page containing parameter 40 Used as select it and set it to Operator unit 1 3 Access Configuration menu 4 Display and access t...

Страница 38: ...at night and or days of the week the parameter can be set to the following values 24h day production at the nominal setpoint 24 hours a day 7 days a week All time programs HC CC production at the nom...

Страница 39: ...K18 unit 6 ERRORS 6 1 LIST OF ERRORS AND TROUBLESHOOTING INSTRUCTIONS Table 6 1 p 39 lists the error codes their descrip tions and priorities which may be generated by the System controller for K18 wh...

Страница 40: ...icated in step 1 Run sensor memorization again as indicated in step 1 5 If step 4 does not resolve the problem Power cycle the System controller if the problem persists contact the Robur technical sup...

Страница 41: ...select the parameter and set it to this value Error code 331 5931 Sensor input BX2 re move the optional sensor connected to input BX2 not used in the standard configurations Error code 332 5932 Senso...

Страница 42: ...s the complete parameter list proceeding as described in Paragraph 4 1 1 p 28 then access the Configuration menu display and access the page containing parameter 6205 Reset to default param eters sele...

Страница 43: ...age SELV for voltage free contacts DC 12 V DC 3 mA Analogue inputs H1 H3 Functional range Internal resistance Safety Extra Low Voltage SELV DC 0 10 V 100 k Pulse count inputs H1 H3 Open contact voltag...

Страница 44: ...puts with short circuit protection 11 3 13 2 V max 88 mA Power GX1 configurable Output voltage 5 V Output voltage 12 V Current Safety Extra Low Voltage SELV outputs with short circuit protection 4 75...

Страница 45: ...data Power supply Bus powered BSB Cabling Power supply and bus solid wire or stranded wire twisted or ferrule 0 25 1 5 mm Room temperature meas urement Measurement range Per EN12098 Range 15 25 C Rang...

Страница 46: ......

Страница 47: ......

Страница 48: ...8111 F 39 035 884165 www robur it robur robur it 29 10 2021 21MCLSDC039 Code D LBR849 Revision B Robur is dedicated to dynamic progression in research development and promotion of safe environmentally...

Отзывы: