background image

2

INSTALLATION INSTRUCTIONS (Cont’d)

5.  Using pipe thread compound suitable for the gas being used, apply 

a small amount on the male pipe threads. (Do not use Teflon tape 
or Teflon compound.) Leave the first two threads clean. Never use 

compound on female threads as it might be pushed into the control 

body.

6.  The gas valve is multi-positional and can be mounted in any position 

(except upside down) without affecting its operation.

7. Install gas valve so gas flow conforms with the inlet and outlet of    
  the control.
8.  

DO NOT insert any object other than suitable pipe or tubing in the 

inlet or outlet of this control. Internal damage may occur and result 
in a hazardous condition. A backup wrench should only be used on 
the wrench boss provided for this purpose (see drawing), never on 
the body of the control, as this could distort the casting. 

NOTE:

 Do not over tighten any pipe connections,

 as this could crack the 

valve body. A valve with a cracked valve body will not be warrantied.

PRESSURE REGULATOR VENT

The 720-079 has a built-in Vent Limiter. The regulator vent is tapped 
1/8” tubing if vent tubing is required. 

CAUTION:

 If bleed tubing is used, 

do not allow main burner or pilot flame impingement on the tubing as 

this will eventually cause clogging of the tubing and improper regula-

tor operation. If bleed tubing is not used, the regulator vent must be 
properly shielded from moisture.

LEAK TEST

Leak test with a soap solution after installing with main burner on. 

 

Coat pipe and tubing joints, gasket, etc. with soap solution. Bubbles 
indicate leaks.

PILOT TUBING

1. Make sure tubing is free of burrs and dirt.
2.  We strongly recommend that the pilot orifice be checked and 

cleaned if necessary at this time.

3.  Connect pilot tubing into the control using fitting provided, and 

tighten for a gas tight seal.

WIRING

DO NOT

 short gas valve terminals. This will damage wall thermostat 

and void warranty.
1.  Check the system for the proper transformer by comparing the VA 

ratings of the transformer and the system. The system rating is 

 

determined by multiplying the voltage draw times the amp draw. 
Normally 20VA 

 

transformers are sufficient for heating only appli cations and 40VA for 

 

heating/cooling applications.

NOTE:

 Improper transformer VA rating will cause erratic system 

 

operation.
2.  Connect the wire from the “MV” terminal on the ignition control unit 

to the “M” terminal on the gas valve.

3.  Connect the wire from the “PV” terminal on the ignition control unit 

to the “P” terminal on the gas valve.

4.  Connect the wire from the “MV/PV” terminal on the ignition control 

unit to the ”C” terminal on the gas valve.

TYPICAL ROBERTSHAW INTERMITTENT PILOT APPLICATION

INSTALLATION INSTRUCTIONS – INTERMITTENT PILOT

Содержание Uni-Kit 720-079

Страница 1: ...Temperature 40 to 175 F Maximum Inlet Pressure 7 W C natural gas 14 W C L P gas REGULATION CAPACITIES SIZE TYPE GAS NATURAL L P MIN MAX MIN MAX 3 8 x 3 8 15 000 175 000 15 000 280 000 1 2 x 3 8 15 000 175 000 15 000 280 000 1 2 x 1 2 15 000 200 000 15 000 320 000 1 2 x 3 4 15 000 200 000 15 000 320 000 3 4 x 3 4 15 000 200 000 15 000 320 000 INTERMITTENT PILOT HOT SURFACE DIRECT SPARK PIPING 1 Che...

Страница 2: ...gging of the tubing and improper regula tor operation If bleed tubing is not used the regulator vent must be properly shielded from moisture LEAK TEST Leak test with a soap solution after installing with main burner on Coat pipe and tubing joints gasket etc with soap solution Bubbles indicate leaks PILOT TUBING 1 Make sure tubing is free of burrs and dirt 2 We strongly recommend that the pilot ori...

Страница 3: ... 1 Check the system for the proper transformer by comparing the VA ratings of the transformer and the system The system rating is deter mined by multiplying the voltage draw times the amp draw INSTALLATION INSTRUCTIONS HOT SURFACE APPLICATIONS Normally 20VA transformers are sufficient for heating only applica tions and 40VA for heating cooling applications NOTE Improper transformer VA rating will ...

Страница 4: ...nt for heating only applica tions and 40VA for heating cooling applications NOTE Improper transformer VA rating will cause erratic system operation 2 Locate the white wire terminal adaptor jumper that is included with the 720 079 gas valve 3 Connect the white wire terminal adaptor to the M and P termi nals on the 720 079 gas valve 4 Determine which wire was connected to the main valve terminal on ...

Страница 5: ...ifications 4 Replace regulator adjustment screw cap A REGULATOR CONVERSION CAUTION Main burner and pilot orifices must be changed when regu lator is converted from one type of gas to another 1 Turn off gas and electricity to appliance 2 Remove slotted cap A adjusting screw B and natural gas spring not color coded C from control 3 Install new L P spring color coded with a black strip 4 Install new ...

Страница 6: ...gon and Uni Line are trademarks of Robertshaw its subsidiaries and or affiliated companies All other brands mentioned may be the trademarks of their respective owners For Technical Service Telephone 1 800 445 8299 Facsimile 1 630 260 7294 TechnicalService robertshaw com www uni line com www robertshaw com 2014 Robertshaw 07 14 1 870 RevC 6 ...

Отзывы: