9.
SETUP AND TEST
1.
Disconnect power to the equipment before pushing the time delay override button.
2.
Cooling Cycle: Set the cooling setpoints of all zone thermostats to their lowest setting.
Note: Ensure that the remote switch selector for mode of operation is not
set to Heat Only (if installed).
a. Press and hold time delay override button. The time delay override is in effect only
when the time delay override button is depressed.
Note: In the time delay override mode, the time factors are reduced by 60 times
(i.e., 1 minute is reduced to 1 second).
b. The LEDs located on the SlimZone Classic panel should indicate the following
condition:
System power ON
Cooling ON
Fan ON
All zone dampers open
3.
Heating Cycle: Set the heating setpoints of all zone thermostats to their highest setting.
Note: Ensure that the remote switch selector for mode of operation is not
set to Cool Only (if installed).
a. The LEDs located on the SlimZone Classic panel should indicate the following
condition:
System power ON
Heating ON
Fan ON (except when plenum option is selected)
R.V. ON
All zone dampers open
4.
Reconnect power to the equipment once test is completed.
5.
Restore zone thermostats to normal setpoints.
SlimZone Classic
12