FUNCTIONAL DESCRIPTION 

 

The Model 563A is a microprocessor based instrument that 
monitors

 

one to eight Vibraswitches. It monitors the 

Vibraswitches to determine the occurrence of excessive 
vibration and then integrates this vibration time. If the 
duration of the excessive vibration exceeds the preset 
limits, an alarm and/or shutdown condition is generated by 
a set of relay contacts. 

 

The Start Time Delay circuitry inhibits monitoring from the 
time a machine is first started until it reaches its normal 
operation speed and condition. This time is adjustable from 
0 to 999 seconds by means of three digital rotary switches. 
The leftmost switch indicates hundreds of seconds, the 
middle switch indicates tens of seconds, and the right 
switch indicates individual seconds. When the machine 
power monitor voltage (normally supplied by the start 
circuit of the machine) is applied to TB-10 and goes from 
OFF to ON, the Start Time Delay is initiated. It can also be 
initiated by pressing and releasing the Pushbutton Indicator 
on the door of the instrument. This delay is terminated at 
the end of the time period specified by the settings of the 
Start Time Delay switches. At the end of the Start Time 
Delay period, the Model 563A will reset all Vibraswitches 
(if required) and commence to monitor them for excessive 
vibration. 

 

A Monitor Time Delay period is initiated when any 
Vibraswitch trips from excessive vibration. The Monitor 
Time Delay period is adjustable from 0 to 99 seconds by 
means of two digital rotary switches. If the vibration 
continues to the end of this period, the alarm and/or 
shutdown contracts will actuate and the red indicator within 
the Reset Button on the instrument door will turn ON. The 
voltage applied to this indicator will also be applied to 
terminals 6 and 7 of TB-9 for an optional remote alarm 
indicator. When this condition occurs, an internal LED will 
come ON. The operator can determine which Vibraswitch 
tripped and cause the alarm and/or shutdown event by 
observing these eight LED's. 

 

The Monitor Time is actually an integrated time period. 
The period is divided into five (5) sampling segments. 
When excessive vibration occurs within a segment, a 
counter is incremented one unit. If no excessive vibration 
occurs during a sampling segment, the counter is 
decremented one unit. The counter is never negative so it is 
either decremented or remains at zero count when there is 
no excessive vibration. If the counter reaches a count of 
five and excessive vibration occurs before it is 
decremented, an alarm and/or shutdown condition is 
generated. 

 

After an alarm and/or shutdown condition occurs, the 
alarmed Vibraswitch will remain tripped until a complete 
"restart" is initiated or the Reset Button on the Model 563A 
cover is pressed and released, which will cause the reset of 
ALL Vibraswitches and the reset of the internal circuitry to 
the initial "Start-up" conditions. This action also returns the 
alarm/shutdown contacts to their normal state and turns off 
the red indicator light and LED. 

The Start Time Delay and the Monitor Time Delay setpoint 
switches and the eight LED's are visible through the 
window on the door so that an observer can determine the 
condition of the individual Vibraswitches and the delay 
settings. 
 

SPECIFICATIONS 

 

PERFORMANCE 

Timing Accuracy

  ..........................................  ±5% @ 68° F 

 
Timing Range

Start Delay

  ...................................  0 to 999 Seconds 

Monitor Delay

 ................................  0 to 99 Seconds 

Setting Resolution

 .................................... 1 Second 

 

ENVIRONMENTAL 

Temperature: 

Operating

  ..................................... -40° F to +160° F 

(-40° C to +72° C) 

Storage

  ........................................  -55° F to +225° F 

 (-49° C to +107° C) 

 
Vibration Limits

  ..................................... 0.5G 15 to 100 Hz 

 
Relative Humidity

 ........................................  95% at 100° F 

 

ELECTRICAL 

 

Supply Voltage

Model 563A-A  ...............  120 VAC ±10%, 50/60 Hz 

150 Watts, 167 VA Maximum 

Model 563A-B  ..............  240 VAC, ±10%, 50/60 Hz 

150 Watts, 167 VA Maximum 

Model 563A-C  ................................. 24 VDC, ±10% 

150 Watts Maximum 

Model 563A-D  ..................................48 VDC, ±10% 

150 Watts Maximum 

 
Machine Power Monitor

Voltage

  ...............................  Same as supply voltage 

Amperage

 ...................................... Less than 20 mA 

 
Alarms/Shutdown Contacts

Terminals 3, 4 & 5 on TB-9 ................ 5 Amp, 28 VDC Res., 

5 Amp, 120 VAC Res., 

1/6 HP (2.2 Amp), 220-240 VAC 

 
Remote Alarm Indicator: 

Terminals 5 & 6 on TB-1 thru TB-8 
and terminals 6 & 7 on TB-9 

Model 563A-A  ........  120 VAC, 25 Watts Maximum 
Model 563A-B  ........ 120 VAC, 25 Watts Maximum, 

1/2 wave rectified  

Model 563A-C  ..........  24 VDC, 25 Watts Maximum 
Model 563A-D  ........... 48 VDC, 25 Watts Maximum  

 
Remote Reset 

Open circuit voltage is 12 Volts Maximum 
Short circuit current is 0.1 Amp Maximum 

Terminals 1 & 2 TB-9 

Содержание 563A

Страница 1: ...digital rotary switches over a range of 0 to 99 seconds Nearly all rotating machinery during its start up operation will go through an excessive vibration point which is inherent to the machine This vibration level sometimes is higher than the alarm shutdown level desired for safe protection The Model 563A contains circuitry which provides a Starting Time Delay to disable the Vibraswitches for a p...

Страница 2: ...he period is divided into five 5 sampling segments When excessive vibration occurs within a segment a counter is incremented one unit If no excessive vibration occurs during a sampling segment the counter is decremented one unit The counter is never negative so it is either decremented or remains at zero count when there is no excessive vibration If the counter reaches a count of five and excessiv...

Страница 3: ...ee Vibraswitches are used it may be more convenient to connect them to terminal blocks 5 6 and 7 The Vibraswitches used with any Model 563A must have reset coils with voltages identical to the primary supply voltage of the Model 563A EXCEPT Vibraswitches used with the 240 VAC version which must have a reset coil voltage of 120 VAC Net Weights With NEMA 4 or 4X enclosure AC units 22 5 lbs 10 2 kg D...

Страница 4: ...EMA 4 2 Explosion proof meets Class I Division 1 Group D 3 NEMA 4X Steel Painted with Gray Epoxy Enamel 4 NEMA 4X Stainless Steel Explosion proof enclosure not supplied with a window or a pushbutton indicator For visual indication to determine which Vibraswitch detected the excessive vibration without removing the cover and or a pushbutton indicator see Accessory Items below ACCESSORY ITEMS Must b...

Страница 5: ...5 ENCLOSURES WEATHER PROOF NEMA 4 DESIGNED FOR SURFACE MOUNTING EXPLOSION PROOF HOUSING MEETS CLASS 1 DIV 1 GROUP D ...

Страница 6: ...6 Q 4105 2 06 Printed in U S A ...

Отзывы: