4.4.3.1.4. TIME
DELAYS
Refer to the Figure 4 - 2 to see the organization
of the Setup Menu. There are two (2) more
variables that can be adjusted from the Setup
Menu. These are the AlarmDly and Ret. Dly,
which are the time delays associated with the
detecting of an alarm and the clearing of an
alarm.
These delays specify the time between the
detection of a change in the alarm state and the
operating of the relay. When an alarm is
detected the time delay will be the time that the
alarm condition must exist before the relay is de-
activated. When a return-to-normal condition is
detected the time delay will be the time the
condition must exist before the relay is activated.
The delays can be turned “off” by setting the
delay to “00” and the active delay times are 1 to
60 seconds. This allows either or both delays to
be turned “Off” and the delay times to be
adjusted independently.
4.4.3.1.4.1.
TIME DELAY ON ALARM
To select the required time delay enter the
Setup Menu, from the normal operating mode by
pressing the [DN] pushbutton, followed be
pressing the [RT] pushbutton. This action will
bring you to the first item in the Setup Menu,
High SP.
Pressing the [DN] pushbutton four (4) times will
bring you to the “AlarmDly” variable. The
display will initially show:
AlarmDly
XX
Where XX represents the currently set time
delay. After a short time the top line of the
display will begin scrolling the message:
“
Relay delay when alarm goes ON
[seconds]
”
Pressing the [RT] pushbutton once will select
the variable. The display will initially show:
AlarmDly
Press RT
Pressing the [RT] pushbutton will open the
variable for change. After a short time the
bottom line of the display will begin to scroll the
message:
“
Press RT to change Alarm delay
”
Pressing the [RT] pushbutton will allow the time
delay to be changed. The display will initially
show:
AlarmDly
XX
*
Where XX* represents the current time delay
setting. After a short time the top line of the
display will begin scrolling the message:
“
Relay delay when alarm goes ON
[seconds]
”
The [UP] and [DN] pushbuttons can be used to
scroll among the possible values. The current
time delay is identified by an “*” appended to the
end of the format. When the desired time delay
value is displayed press the [RT] pushbutton to
select that value. The display will return to the
previous level of the Setup menu.
4.4.3.1.4.2.
TIME DELAY ON ALARM
CLEAR
To select the required time delay enter the
Setup Menu, from the normal operating mode by
pressing the [DN] pushbutton, followed be
pressing the [RT] pushbutton. This action will
bring you to the first item in the Setup Menu,
High SP.
Pressing the [DN] pushbutton five (5) times will
bring you to the “Ret. Dly” variable. The display
will initially show:
Ret. Dly
XX
Where XX represents the currently set time
delay. After a short time the top line of the
display will begin scrolling the message:
“
Relay delay when alarm goes OFF
[seconds]
”
Pressing the [RT] pushbutton once will select
the variable. The display will initially show:
Ret. Dly
Press RT
Pressing the [RT] pushbutton will open the
variable for change. After a short time the
bottom line of the display will begin to scroll the
message:
“
Press RT to change return dela
y
”