background image

TF-S

ERIES

 I

NSTALLATION

, O

PERATION

 

AND

 S

ERVICE

 M

ANUAL

12 

6.4 TF-160 - Single Elbow Design (Individual Vents)

6.5 TF-160 Double "L" Design (Individual Vents)

6.6 TF-250 - Combination "L" and "U" Design (Individual Vents)

Burner

Tube

I

ndividual

 

Vent

90° 

Elbow

10' 

Typ.

(3 

m

)

Содержание Vantage TF TF-120

Страница 1: ...e installation and service of gas fired heating equipment or your gas supplier Improper installation adjustment alteration service or maintenance can result in death injury or property damage Read the Installation Operation and Service Manual thoroughly before installing or servicing this equipment Installer Please take the time to read and understand these instructions prior to any installation I...

Страница 2: ......

Страница 3: ...Installation 21 7 6 Reflector Installation 21 SECTION 8 Optional Heater Accessories 23 8 1 U Tube Configuration 23 8 2 Elbow Package Configuration 26 8 3 Reflector Side Extension 28 8 4 Lower Clearance Shield Installation 29 8 5 Two Foot Decorative Grille Installation 29 8 6 One Foot Decorative Grille Installation 31 8 7 Protective Grille Installation 33 SECTION 9 Venting 34 9 1 Venting Requiremen...

Страница 4: ......

Страница 5: ...6 Figure 9 Lower Clearance Shield 6 Figure 10 Venting 6 Figure 11 Major Component Descriptions 8 Figure 12 Critical Hanger Placement 14 Figure 13 Linear Heater Assembly Overview 15 Figure 14 Linear Heater Layout Overview 16 Figure 15 Linear Heater Layout Overview Continued 17 Figure 16 U Tube Heater Assembly Overview 23 Figure 17 U Tube Heater Layout Overviews 24 Figure 18 U Tube Heater Layout Ove...

Страница 6: ......

Страница 7: ... residential spaces These instructions the layout drawing local codes and ordinances and applicable standards that apply to gas piping electrical wiring venting etc must be thoroughly understood before proceeding with the installation Thin sheet metal parts including the aluminum reflector portion of the heater and the various venting components have sharp edges To prevent injury the use of work g...

Страница 8: ...e back cover For an immediate solution you may affix this copy on the wall near the heater Know your model number and installed configuration Model number and installed configuration are found on the burner and in the Installation Operation and Service Manual See Page 3 Figure 1 through Page 6 Figure 10 Write the proper clearance dimensions in permanent ink according to your model number and confi...

Страница 9: ...e maximum permissible stacking height to maintain required clearances from the heater to the com bustibles Signs must be posted adjacent to the heater thermostat In the absence of a thermo stat signs must be posted in a conspicuous location Consult local Fire Marshal Fire Insurance Carrier or other authorities for approval of proposed installation when there is a possibility of exposure to combust...

Страница 10: ... 219 176 TF 350 8 9 88 73 21 23 224 186 TF 380 8 9 88 73 21 23 224 186 A C D B FIGURE 3 TWO SIDE REFLECTORS inches centimeters Model A B C D A B C D TF 120 6 23 66 23 16 59 168 59 TF 160 6 25 72 25 16 64 183 64 TF 200 6 27 78 27 16 69 199 69 TF 250 6 32 84 32 16 82 214 82 TF 300 6 35 88 35 16 89 224 89 TF 350 8 40 91 40 21 102 232 102 TF 380 8 40 91 40 21 102 232 102 A C D B FIGURE 4 45 TILT REFLE...

Страница 11: ...0 TF 350 8 54 87 51 21 138 221 130 TF 380 8 54 87 51 21 138 221 130 A C D B FIGURE 6 U TUBE 45 inches centimeters Model A B C D A B C D TF 120 8 8 60 42 21 21 153 107 TF 160 8 8 66 46 21 21 168 117 TF 200 8 8 74 52 21 21 188 133 TF 250 8 8 78 61 21 21 199 155 TF 300 8 8 84 66 21 21 214 168 TF 350 8 8 85 70 21 21 216 178 TF 380 8 8 85 70 21 21 216 178 B C D A FIGURE 7 U TUBE OPPOSITE 45 REFLECTOR i...

Страница 12: ...38 16 97 168 97 TF 200 6 40 71 40 16 102 181 102 TF 250 6 46 77 46 16 117 196 117 TF 300 6 50 80 50 16 127 204 127 TF 350 8 52 82 52 21 133 209 133 TF 380 8 52 82 52 21 133 209 133 A C D B FIGURE 9 LOWER CLEARANCE SHIELD inches centimeters Model A B C D A B C D TF 120 6 39 33 39 16 100 84 100 TF 160 6 40 38 40 16 102 97 102 TF 200 6 50 44 50 16 127 112 127 TF 250 6 54 48 54 16 138 122 138 TF 300 6...

Страница 13: ...ns shall be made to assure accessibility to suspended heaters for recurrent maintenance purposes 4 3 Public Garages Installation in garages must be in accordance with the following codes United States Standard for Parking Structures NFPA 88A latest revision or the Code for Motor Fuel Dispensing Facilities and Repair Garages NFPA 30A latest revision Canada Refer to CAN CGA B149 1 and B149 2 Install...

Страница 14: ...ith Lock Reflector End Cap Punch out center section to accommodate tube Tube and Reflector Hanger Suspend system from these hangers Flex Gas Line with Shut Off Cock Tube Hot Rolled or Heat Treated Aluminized Tube Supplied in 10 3 m lengths Burner Tube Supplied in 10 3 m lengths Burner tube is always the first tube after the burner Reflector Support Strap Wire Form Turbulator Turbulator must be ins...

Страница 15: ...eel Reflector Part No Description 20 6m 30 9m 40 12m 20 6m 30 9m 40 12m 20 6m 30 9m 40 12m 10 3m 20 6m 30 9m 40 12m 10 3m 20 6m 30 9m 40 12m 10 3m 20 6m 30 9m 40 12m 91409300 Tube Hot Rolled Steel 10 3m 1 2 3 1 2 3 4 91409408 Tube HT Aluminized 10 3m 1 2 3 1 2 3 1 2 3 4 1 2 3 4 03051101 Burner Tube ALUMI THERM Steel 10 3m 1 1 1 1 1 1 03051601 Burner Tube HT ALUMI THERM Steel 10 3m 1 1 1 01312700 C...

Страница 16: ... Tubing Length Each Side Core Packages 2 Required Model Minimum Hot Rolled with Aluminum Reflector Aluminized with Aluminum Reflector Aluminized with Stainless Steel Reflector TF 120 20 6 m CP20HRS CP20ALUM CP20ALUMSS TF 160 20 6 m CP20HRS CP20ALUM CP20ALUMSS TF 200 30 9 m CP30HRS CP30ALUM CP30ALUMSS TF 250 40 12 m CP40HRS CP40ALUM CP40ALUMSS TF 300 50 15 m CP30HRS EXP20HRS CP30ALUM EXP20ALUM CP30...

Страница 17: ...hey are in the guidelines of this manual When designing a U Tube or Elbow configuration the following rules must be adhered to A minimum of 10 3 m of tubing on TF 120 160 and or a minimum of 15 4 5 m of tubing on the TF 200 250 300 350 380 is required between the burner and the Elbow or U Tube The design and installation must adhere to the rules and guidelines located in this manual See Section 7 ...

Страница 18: ...PERATION AND SERVICE MANUAL 12 6 4 TF 160 Single Elbow Design Individual Vents 6 5 TF 160 Double L Design Individual Vents 6 6 TF 250 Combination L and U Design Individual Vents Burner Tube Individual Vent 90 Elbow 10 Typ 3 m ...

Страница 19: ...ing The heaters must be installed in accordance with clearances to combustibles as indicated on the rating plate and in this instruction manual The minimum and maximum gas inlet pressures must be maintained as indicated on the rating plate Typical installation configurations are shown on Page 14 Figure 12 Expansion and contraction of the tube dictates that the minimum suspension lengths in the tab...

Страница 20: ...ed Description Part Number S Hook 91907302 Tube Reflector Hanger 03090100 Total Straight Length both sides or Length from U Tube to U Tube in a Double U Layout Typical Expansion Each Side Minimum X Length 0 50 1 3 cm 12 31 cm 51 60 2 5 cm 18 46 cm 61 80 3 8 cm 24 61 cm 81 100 4 10 cm 30 76 cm 101 120 5 13 cm 36 91 cm 121 140 6 15 cm 42 107 cm 141 160 7 18 cm 48 122 cm If the installation requires ...

Страница 21: ...0 in lb 13 56 Nm Tube Clamp Bolt Reflector Reflector End Cap Tube Reflector Support Burner Tube Burner Tube Clamp Package Coupling U Clips Flexible Boot Burner Tube Tube and Reflector Hanger For shorter than minimum suspension lengths tube clamps must be used at the two farthest hangers on each side of the burner ...

Страница 22: ...cap to burner c 2 5 cm end cap to hanger d 7 6 229 cm distance first hanger e 10 305 cm distance between hangers f 9 5 24 cm burner height g 23 5 60 cm burner length f c b d e e 30 9 m Tube Length Each Side g f c b d e e e 40 12 m Tube Length Each Side g f g c b d e 20 6 m Tube Length Each Side c b d e e e e 50 15 m Tube Length Each Side f g Linear layouts showing one side Use same measurements fo...

Страница 23: ...STALLATION 17 FIGURE 15 Linear Heater Layout Overview Continued c b d e e e e e 60 18 m Tube Length Each Side f g b c d e e e e e e 70 21 m Tube Length Each Side b f g b c d e e e e e e b 80 24 m Tube Length Each Side f g ...

Страница 24: ...m NOTE Tubing requires a downward slope of 1 2 13 mm per 20 6 m away from burner Weld Seam must be to the bottom of the tube Offset mounting hole must be to the top Description Part Number Burner Tube 03051XXX S Hook 91907302 Tube Reflector Hanger 03090100 Lock Washer Gasket Burner Bolt Description Part Number Bolt 94273914 Lock Washer 96411600 Gasket 02568200 Burner 090XXXXX ...

Страница 25: ... Washer 95211600 Nut 92113900 Tube Tube Orient coupling so that the impact block is in the 2 00 or 10 00 o clock positions Closed Open Tab 3 8 cm to 4 10 cm Slide Bar Coupling Lock Coupling Wide end Coupling Tube Slide Bar Coupling Lock A Close coupling with tab B Start Slide bar Coupling Lock onto coupling C Insert tubes into coupling D Tighten coupling to join tubes Description Part Number Coupl...

Страница 26: ... tight End of Slide Bar should be within tolerance listed below Repeat Step 7 4 A D until all tubes are assembled See Page 20 Section 7 4 2 Tighten slide bar as shown below 10 Typ 1 254 cm Typ 25 cm 7 6 1 229 cm 25 cm Model Minimum Tube Length Per Side TF 120 20 6 m TF 160 20 6 m TF 200 30 9 m TF 250 40 12 m TF 300 50 15 m TF 350 50 15 m TF 380 60 18 m See recommended venting lengths on Page 34 Se...

Страница 27: ... 2 5 03051504 Tube 91409XXX Turbulator must be installed in the last standard section of tube Turbulator Installation Model Tube Section TF 120 2nd 10 Section Each side TF 160 2nd 10 Section Each side TF 200 3rd 10 Section Each side TF 250 N A TF 300 N A TF 350 N A TF 380 N A Model Each Side TF 120 TF 160 1 03051503 4 03051504 TF 200 1 03051503 2 03051504 Burner Hanger Burner Tube Reflector Descri...

Страница 28: ...ng a reflector support with loose screws at the reflector overlap 3 The remaining reflector overlaps require a non slip overlap connection To affix the reflectors together in a non slip overlap either a use reflector support and tight screws b if both reflectors lay inside a hanger u clips or sheet metal screws may be used This section of three reflectors joined together must be affixed to the tub...

Отзывы: