ROBERTS GORDON
®
ULTRAVAC™ C
ONTROLLER
I
NSTALLATION
M
ANUAL
42 of 65
the password must be entered in order to access the
parameters again.
7.2 Lenze VFDs
The drive can be reset to the "factory" default settings
or set according the system characteristic.
START BUTTON: This button will start the drive.
STOP BUTTON: Stops the drive, regardless of which
mode the drive is in.
ROTATION: In Local Mode (P100 = 0, 4, 6), this
selects the motor rotation direction:
- The LED for the present rotation direction (FWD or
REV) will be on
- Press R/F; the LED for the opposite rotation direc-
tion will blink
- Press M within 4 seconds to confirm the change
- The blinking direction LED will turn on, and the
other LED will turn off
NOTE:
Confirm pump rotation matches arrow
stamped on pump housing.
Rotation is set in P112. When P112 = 0, rotation is
forward only. When P112 = 1 rotation is forward and
reverse.
MODE: Used to enter/exit the Parameter Menu when
programming the drive and to enter a changed
parameter value.
UP AND DOWN BUTTONS: Used for programming
and can also be used as a reference for speed, PID
setpoint, or torque setpoint.
When the UP and DOWN buttons are the active ref-
erence, the middle LED on the left side of the display
will be on
To go to the PROGRAM mode and access the
parameters, press RUN button, then follow the VFD
parameter below and use the local keypad and dis-
plays below to set the parameters.
Parameter Number
Parameter Name
Factory Default
New Setting
AC-Teck
Lenze
AC-Teck
Lenze
AC-Teck
Lenze
AC-Teck
Lenze
P01
P107
Line Voltage
01
01
01
01
P02
-
Carrier Frequency
02
-
02
-
P03
P110
Start Method
01
0
05
05
P05
P101
Standard Speed Source
01
0.0
(03) (0-10)VDC
(04) (4-20)mA
(01) for 0-10VDC
(02) for 4-20mA
P44
P194
Password
225
0.0
Any# 000-999
Any# 000-999
P45
P102
Speed at Minimum Signal
0.0 Hz
00
Frequency
Setting Noted
Frequency Setting
Noted on Page
P46
P103
Speed at Minimum Signal
60.0 Hz
60.0
Frequency
Setting Noted
on Page
Frequency Setting
Noted on
Содержание UltraVac URVBNC
Страница 2: ......
Страница 4: ......
Страница 7: ...SECTION 1 INTRODUCTION 3 of 65 FIGURE 1 Connected Components ...
Страница 8: ...ROBERTS GORDON ULTRAVAC CONTROLLER INSTALLATION MANUAL 4 of 65 Connected Components continued ...
Страница 21: ...SECTION 2 SPECIFICATIONS 17 of 65 FIGURE 4 Variable Frequency Drive Components Factory pre wiring shown ...
Страница 44: ...ROBERTS GORDON ULTRAVAC CONTROLLER INSTALLATION MANUAL 40 of 65 FIGURE 24 ULTRAVAC Unitary Internal Diagram ...
Страница 48: ...ROBERTS GORDON ULTRAVAC CONTROLLER INSTALLATION MANUAL 44 of 65 FIGURE 25 End Vent Vacuum ...
Страница 52: ...ROBERTS GORDON ULTRAVAC CONTROLLER INSTALLATION MANUAL 48 of 65 FIGURE 27 Troubleshooting Flow Chart ...
Страница 53: ...SECTION 9 TROUBLESHOOTING 49 of 65 Troubleshooting Flow Chart continued ...
Страница 54: ...ROBERTS GORDON ULTRAVAC CONTROLLER INSTALLATION MANUAL 50 of 65 Troubleshooting Flow Chart continued ...
Страница 55: ...SECTION 9 TROUBLESHOOTING 51 of 65 Troubleshooting Flow Chart continued ...
Страница 56: ...ROBERTS GORDON ULTRAVAC CONTROLLER INSTALLATION MANUAL 52 of 65 FIGURE 28 Troubleshooting Flow Chart Repeater ...
Страница 57: ...SECTION 9 TROUBLESHOOTING 53 of 65 FIGURE 29 Troubleshooting Flow Chart BACnet ...
Страница 65: ......
Страница 66: ......