3.10 Outdoor Sensor (P/N 10081500) Placement
The outdoor sensor measures air temperature out-
side the building. It is important that the sensor is
located on the outside of the building on the north
facing wall. Failure to mount the sensor on the north
facing wall will result in artificially high temperature
readings and failure to modulate as designed. If pos-
sible, locate the sensor high under an eve to prevent
incorrect readings from direct sunlight and damage
due to the elements.
FIGURE 12: Outdoor Sensor Placement
Mount the outside sensor with the sensor module
facing down to prevent accumulation of dirt or water.
3.11 Outside Air Supply (P/N 90707501K)
If an outside air (O.A.) blower is to be used, modifica-
tions to the outside air blower out-of-box wiring must
be made to properly time, and safety check the
blower with the main pump.
for external wiring details.
Remove the internal connection between the pres-
sure switch (P.S.) and the relay and wire the P.S. of
the O.A. Blower in series with that of the main pump.
Send 24V from Terminal Block 2 in the controller to
terminals T1 and T2 in the O.A. Blower. Power the
blower with its own 120V, 15A, 60Hz supply.
for
wiring.
North
Outside
Sensor
Sensor
Module
facing down
Содержание CORAYVAC
Страница 2: ......
Страница 4: ......
Страница 69: ...SECTION 8 PROGRAMMING AND TROUBLESHOOTING THE SYSTEM 65 THIS PAGE LEFT INTENTIONALLY BLANK ...
Страница 71: ...SECTION 9 TROUBLESHOOTING 67 FIGURE 26 Vacuum pump does not turn on ...
Страница 73: ...SECTION 9 TROUBLESHOOTING 69 FIGURE 28 VFD showing a fault sign FIGURE 29 VFD input power issue ...
Страница 75: ...SECTION 9 TROUBLESHOOTING 71 FIGURE 31 Burner troubleshooting in manual mode ...
Страница 77: ...SECTION 9 TROUBLESHOOTING 73 After 45 second prepurge burners do not light continued ...
Страница 79: ...SECTION 9 TROUBLESHOOTING 75 FIGURE 34 APS does not close within 60 seconds after VFD receives run command ...
Страница 81: ...SECTION 9 TROUBLESHOOTING 77 FIGURE 36 Air Pressure Switch alarm ...
Страница 83: ...SECTION 9 TROUBLESHOOTING 79 FIGURE 38 Repeater troubleshooting ...
Страница 85: ...SECTION 9 TROUBLESHOOTING 81 BACnet MS TP troubleshooting continued ...
Страница 109: ...SECTION 13 TOUCHSCREEN TREE 105 Touchscreen Tree Overview continued ...
Страница 111: ...SECTION 13 TOUCHSCREEN TREE 107 FIGURE 47 Maintenance Unit FIGURE 48 Alarms ...
Страница 113: ...SECTION 13 TOUCHSCREEN TREE 109 FIGURE 51 Configuration Zones FIGURE 52 Configuration Unit ...
Страница 115: ...SECTION 13 TOUCHSCREEN TREE 111 FIGURE 55 Touchscreen System FIGURE 56 Touchscreen Setup ...
Страница 118: ...ROBERTS GORDON CORAYVAC MODULATING HEATING CONTROL CONTROLLER INSTALLATION MANUAL 114 ...
Страница 119: ...SECTION 14 THE ROBERTS GORDON CORAYVAC COMPLETE MODULATING HEATING CONTROL LIMITED WARRANTY 115 ...