Before Using the Heater
8
CARIBE
®
GTH SERIES HEATER
Electrical Service
The CARIBE
®
GTH heater requires a grounded three-prong
electrical outlet to be installed within 18 inches of the rear surface
of the heater’s burner box. It is recommended that the outlet for the
heater be ceiling-mounted and should be on a dedicated circuit.
DO NOT use an electrical extension cord to operate the heater.
Heater Rating: 120 VAC, 60 Hz, Single Phase, 1 Amp
System
Requirements
The heater must be electrically grounded in accordance with the
following codes: United States: Refer to National Electrical Code,
ANSI/NFPA-70 - latest revision. Wiring must conform to the most
current National Electrical Code and local ordinances. Canada:
Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest
revision.
Grounding
Electrical Shock Hazard
Plug heater into grounded three-prong
ceiling receptacle.
Do not cut or remove the grounding
prong from this plug.
Do not use with an extension cord.
Failure to follow these instructions will
result in death or electrical shock.
Risque d’électrocution
Brancher le cordon du radiateur sur un
socle à 3 broches et à la masse, situé
au plafond.
Ne pas sectionner ou retirer la broche
de masse de cette prise.
N’utiliser aucun câble de rallonge.
Le non-respect de ces consignes peut
entraîner mort ou électrocution.
ATTENTION
WARNING
©
Printed in the U.S.A P/N 91037500 Rev. A
It is important to note that the CARIBE
®
GTH heater is controlled by
a low voltage (24 VAC) thermostat supplied with the heater. The
Direct Spark Ignition (DSI) module located inside the burner box
supplies the necessary electrical power to operate the thermostat.
No other electrical power to the thermostat is required.