6.1.1
A gas meter is connected to the service pipe by the
Gas Supply Company. An existing meter should be
checked, preferably by the Company to ensure that
the meter is adequate to deal with the rate of gas sup-
ply required.
6.1.2
Installation pipes should be fitted in accordance with
National Standards. Pipework from the meter to the
heater(s) must be of adequate size. Pipes of smaller
size than the heater inlet gas connection should not
be used.
6.1.3
Connect the heater to the gas supply ensuring that the
final connections are as follows:
a) Gas supply pipework is run in medium or heavy
gauge tubing to National Standards terminating in
a Rc1/2 (1/2") BSP thread within 300 mm of the
heater gas inlet.
b) An Rc1/2 (1/2" BSP) mm union cock should be
used and fitted into the supply adjacent to the
heater.
c) A flexible metal hose is connected directly to the
Rc1/2 (1/2" BSP int) connection on the burner.
This metallic hose must conform to National
Standards.
6.1.4
IMPORTANT
- The complete installation must be
tested for gas soundness in accordance with National
Standards.
Figure 14.
Typical Gas Line Installation (Install According to National Standards)
300 mm
Burner Box
Flex Line Connector
Stainless Steel Flexible Hose
500 mm long
Minimum bend radius 140 mm
Shutoff Cock
REAR VIEW
DOOR-SIDE VIEW
45
°
45
°
6
6..2
2
E
EL
LE
EC
CT
TR
RIIC
C S
SU
UP
PP
PL
LY
Y
6.2.1
Connect to the electrical supply using a 3 pin plug via
a locally mounted double pole fused switch having a
minimum disconnection of 3 mm on each pole. This
switch should be fused to 3 amps. The burner is fused
at 2 amps. There are no control connections in the
standard burner. Control is affected by interruption of
the main power inlet. See Figures 15 and 16 for the
external wiring details for the single-burner and double
linear heater systems.
6.2.2
All wiring must comply with current I.E.E. Wiring
Regulations and any local regulations which may
apply. Always switch off the supply to the burner and
disconnect by removing the plug before removing the
burner side panel.
6.2.3
In compliance with EN416 clause 4.1.9 Electrical
Operational Safety, any temperature and time control
must be located in the heated area.