8. 

Commissioning 

 

8.1. 

Assembling position 

 

8.2. 

Preliminary steps 

 

Check that the unit is correct for the local mains supply (rating plate information) and that it is correctly rated 
for the feed system.  

 

Connect the controller according to the connection diagram 

 

When  applications  with  frequently  on  and  off  cycles  are  required,  use  the  intended  enable  input.  It  is 
prohibited to open the current circuit with a switch or a contactor while the feeder is running. 

8.2.1.  Important points 

Using  the  control  units  described  in  this  document,  it  is  possible  to  adjust  the  feed  system  that  it  runs  in 
resonance. In this condition it is possible to obtain excessive output for a very low set point setting. Therefore 
extreme care should be taken to avoid causing damage to the drive coil, through hammering.  
 

In practice it is not possible to run at resonant frequency without accelerometer feedback because the system would be 
unstable  and  uncontrollable.  The  system  must  be  set  safely  off  resonance  i.e.  either  above  or  below  the  natural 
frequency.  
 

Resonant frequency:

 Depending on the spring and mass design of the feeder system it is possible to have resonance 

at more than one frequency. These additional resonance points are multiples of the main frequency. For this reason in 
critical situations it is possible that the automatic frequency search will not find true resonance and in such cases the 
natural frequency must be determined manually. 

8.2.2.   Operating frequency of the feeder coil 

It is possible that the current flowing through the coil will increase for a small frequency adjustment. and so this should 
be checked with a true RMS instrument for each new application as well as monitoring the coil for heat build-up.  
The coil should be designed for the correct operating frequency to prevent excessive current draw and the consequential 
overloading of the coil. 

8.2.3.  Measurement of the output voltage and current 

The voltage and current cannot be measured with a regular instrument because the controller output uses an electronic 
inverter with a pulse width modulation signal. An effective measuring instrument such as a moving iron meter (analog) 
must be used. It is recommended that an analog instrument is used rather than an electronic multi-meter which will give 
a misleading reading. 

8.3. 

Putting the equipment into operation 

1.  Establish the vibrating frequency. 
2.  Establish the power of the feed system (maximum permissible current draw).  

 
For a new feeder where settings are unknown: (see also comments below) 

Without connecting the feeder

, select parameter FAC in menu C210 (reset factory settings), press the cursor key to 

reset (SAFE) and press the P key to leave the menu. The factory settings are listed in the table in section 7, headed 
settings 

! Comments ! 

It  is  possible  that a  special  parameter  set,  for  a  machine  manufacturer,  has  been  pre-stored  under  a  user  code  and 
these can be recalled. In such instances specific machine settings will be loaded and so the next steps are not relevant. 
 
Basic settings: 
 

 

Connect  feeder. 

 

Set frequency (refer to feeder data sheet). Menu C096 parameter F.  

 

Check  current  limit  (refer  to  feeder  data  sheet).  Menu  C040  parameter  I  (shows  the  current  limit  as  a 
percentage of maximum). If applicable use service menu for setting. 

 

Increase set point, observe feeder, check running.  

 

Attention

 

Please fasten the devices on a vibration-free underground and take care for sufficient air circulation. 
 

Содержание ESM 3000 Series

Страница 1: ...Operating Instructions Controller for vibratory drive systems ESR 3000 ESM 3000...

Страница 2: ...s 11 8 2 2 Operating frequency of the feeder coil 11 8 2 3 Measurement of the output voltage and current 11 8 3 Putting the equipment into operation 11 9 Setting Instructions 12 9 1 User adjustment of...

Страница 3: ...014 35 EU and Electromagnetic Compatibility Directive 2014 30 EU We hereby declare that the product meets the following requirements Low Voltage Directive 2014 35 EC Electromagnetic Compatibility Dire...

Страница 4: ...tection of the described product and connected equipment Isolate from mains before installation or dismantling work as well as for fuse changes or post installation modifications Observe the prescribe...

Страница 5: ...g frequency is also dynamically adjusted to compensate for resonant frequency changes caused by load changes In normal operating mode without accelerometer the feeder remains constant at the set frequ...

Страница 6: ...ent of these sensitive parameters An interface option can be used to provide an RS232 or Fieldbus Profibus DP connection 2 1 Track control The output can be switched ON and OFF from a track component...

Страница 7: ...ime Out message active if after adjusted time no material is recognized by the sensor adjustable with parameter E not on 16 A units 2 3 6 Air valve output 24 VDC Output for air blast comes on with fee...

Страница 8: ...Operating temperature 0 45 C Storage temperature 10 80 C Altitude 1000 m 0 5 rated current reduction for each additional 100 m The units are provided with switch on current damping However it is stil...

Страница 9: ...1 Sec 020 096 Soft stop ramp down 0 60 Sek 0 1 Sek 020 096 Switch to external set point 0 I E S P 0 003 Set point 0 4 20 mA 0 I 4 20 0 003 Potentiometer set point 0 I POT 0 003 Coarse Fine control 0 I...

Страница 10: ...thorized adjustment the adjustment parameters in the user menus are protected A code must be entered to open the user menus There are different pass codes for each function group Setting adjustments a...

Страница 11: ...ncy adjustment and so this should be checked with a true RMS instrument for each new application as well as monitoring the coil for heat build up The coil should be designed for the correct operating...

Страница 12: ...quency otherwise on hitting the resonant frequency it is possible to achieve a high amplitude with a low output voltage An analog effective value current indicating unit moving iron meter must be conn...

Страница 13: ...m limit 1 Adjust set point to zero 2 Set parameter P maximum limit to 50 3 Adjust set point to 100 4 Increase the limit P from 50 until the required amplitude is reached 5 The full set point range of...

Страница 14: ...e out not active I Sensor time out active E Sensor time out sec P P P P P P P P P P F Running mode P 0 Sensor time out not active I Sensor time out active E Sensor time out sec P P P Code C 015 P Runn...

Страница 15: ...ting unit moving iron meter must be connected into the output circuit Resonant frequency is reached when there is a maximum amplitude for a minimum output current To achieve a stable feed system there...

Страница 16: ...EN_2020 07 05 2020 SJ I Hide menus Running mode P P P P 9 2 9 Recall user or factory settings Code C 210 9 2 10 Hide parameter menus Code C 117 Return to factory settings Return to user settings Runni...

Страница 17: ...y during setting up Sensor fault only when regulation mode is selected Accelerometer not working or faulty ERROR Reset through Menu C009 Sensor time out After sensor time out has elapsed ERROR Reset i...

Страница 18: ...e input socket X5 Status output socket X1 Output Feeder X0 Main supply 110 240 V 50 60 Hz 1 24 V 3 GND 4 Input 1 2 3 4 1 2 3 PE 1 24 V 2 Input 3 GND 1 2 3 4 1 24 V 3 GND 4 Input 1 2 3 4 1 L 2 N 3 nc 4...

Страница 19: ...Accelerometer 5 6 7 1 2 3 4 8 9 E 24V E S A 10k 0 10V 0 4 20mA 7 8 7 8 R 500 OHM extern 10V 12 24V DC 4 5 21 22 23 55 54 53 52 51 27 26 29 28 25 24 INPUT GND 24 V SW 31 32 33 34 35 36 37 L N A2 A1 PE...

Страница 20: ...for 6 A panel mounting versions Recommended method of terminating screen of output cable The output cable to the feeder must be screened to conform with EMC regulations When a potentiometer is connect...

Страница 21: ...Rhein Nadel Automation GmbH 21 VT BA ESR ESM3000 EN_2020 07 05 2020 SJ 13 Dimensions Enclosed construction Enclosed construction 6A Enclosed construction 12A...

Страница 22: ...Rhein Nadel Automation GmbH 22 VT BA ESR ESM3000 EN_2020 07 05 2020 SJ 13 1 Dimensions Panel mounting...

Страница 23: ...voltage limit allows 110v coils to be used on a 230V supply without damage Parameter Display Factory setting Entry code Enable service menu 0 I En C 0 127 Adjust current limit 0 100 I 100 040 Set low...

Страница 24: ...in parallel the coil current is the sum of all individual currents Enable Service Mode The actual service menu is accesed by opening the service mode The normal service menu containing the output cur...

Страница 25: ...6 CH 3360 Herzogenbuchsee Switzerland Phone 41 0 62 956 10 00 Fax 41 0 62 956 10 10 E mail info handling systems ch www handling systems ch Manufacturing and Sales Pol Ind Famades c Energia 23 E 08940...

Отзывы: