Rhein - Nadel Automation GmbH 

    5 

   

 

 

    14.04.14 

VT-BA EBC 3000GB 

 

 
 
 
 

 

Before opening the control unit 

pull the mains plug! 
Then wait 10 min. until the power pack is discharged.

 

 
Connection is done on the XK1 terminal strip. 
 
In control mode with 0-10 volts  
onto terminal XK1.3 +10 volts 
Terminal XK1.5 GND  
 
In control mode with 0-20mA  
onto terminal XK1.4 +20mA 
Terminal XK1.5 GND  
 

3.2.1   Reversing mode 

 
Before connecting, the right-hand side panel of the unit has to be opened. 
 
 
 
 

 

Before opening the control unit 

pull the mains plug! 
Then wait 10 min. until the power pack is discharged.

 

 
To  activate  the  reversing  mode,  connect  a  voltage-free  contact  onto  terminals  XK1.9  and  XK1.8.  When  switching  the 
sense of rotation, the motor stops a moment and then starts in the opposite moving direction at the set speed. If the sense 
of rotation is reversed without switching or if the contact is open, the motor will run in the set sense of rotation. 
 

3.3 

Release of the function through external components 

 
The  standard  adjustment  of  the  control  unit  makes  sure  that  the  oscillating  belt  drive  starts  when  the  mains  switch  is 
switched on. If the control unit is to operate without disconnection from the mains in the Start-Stop mode, the control unit 
is to be opened by observing the above-mentioned safety notes. The blind plug at the side of the case replaces a screw 
fitting with strain relief size M16. This is where the cable for the release is lead through. There are two possible ways of 
performing a release: 
 

Release through a contact

 

The way this simple and economical solution works is that a contact releases the control unit by closing and the belt drive 
runs. The connection is made on terminals 7 and 9; the jumper put in at the works is to be removed. At the same time, 
please remember the following: 

  There  is  voltage  in  the  connection!  Cable  type  and  colour  as  well  as  insulation  regulations  must  be  observed;  the 

contact must, of course, be voltage-free. 

  The  cable  may  not  be  installed  in  the  immediate  vicinity  of  high-energy  switching  equipment  or  strong  interference 

fields. 

 

Release through a voltage signal 

The signal is connected to terminals 6 - and 7 +; the jumper, i.e. terminals 7 and 8, have to be removed. The drive starts 
when there is a signal between 10 and 30 volts DC in correct polarity. The input is protected against wrong polarity. The 
use of an optocoupler in the control unit makes the input voltage-free and allows one to install unshielded cables of almost 
any length. However, high-energy interferences must be avoided here too. 

Содержание EBC 3000

Страница 1: ...Rhein Nadel Automation GmbH 1 14 04 14 VT BA EBC 3000GB Operating Instructions Control Units for Belt Drives EBC 3000 BA Rhein Nadel Automation GmbH ...

Страница 2: ...ction Diagram 6 Declaration of Conformity in terms of the Low Voltage Directive 2014 35 EU and the EMC Directive 2014 30 EU We herewith declare that the product is in conformity with the following provisions Low Voltage Guideline 2014 35 EU EMC Directive 2014 30 EU Applied harmonised standards DIN EN 60204 T1 EN 61439 1 Comments Rhein Nadel Automation Managing Director Jack Grevenstein ...

Страница 3: ...nse of rotation of the connected motor The control unit is designed for a mains voltage from 110 volts AC to 230VAC The control unit checks the mains voltage and adjusts itself automatically 1 2 EC Conformity The control unit complies with the following regulations EMC Directive 2014 30 EU Low Voltage Guideline 2014 35 EU Applied harmonised standards EN 60204 T 1 EN 61439 1 1 3 Technical data Powe...

Страница 4: ... checked Is the control unit properly closed with all its screws Are the existing plug in fixing devices locked into place screwed tight Are all cables and bushings intact Is the INTENDED USE guaranteed Does the indicated supply voltage on the control unit conform with the local power supply network The control unit may only be put into operation if all above questions can clearly be answered with...

Страница 5: ...n from the mains in the Start Stop mode the control unit is to be opened by observing the above mentioned safety notes The blind plug at the side of the case replaces a screw fitting with strain relief size M16 This is where the cable for the release is lead through There are two possible ways of performing a release Release through a contact The way this simple and economical solution works is th...

Страница 6: ...Rhein Nadel Automation GmbH 6 14 04 14 VT BA EBC 3000GB 4 Dimensioned Drawing 5 Connection Diagram ...

Страница 7: ...ch Hall Tel 49 0 791 9460098 0 Fax 49 0 791 9460098 29 Email info psa zt de HSH Handling Systems AG Wangenstr 96 CH 3360 Herzogenbuchsee Tel 41 062 95610 00 Fax 41 062 95610 10 Internet www rna de Email info handling systems ch RNA AUTOMATION LTD Hayward Industrial Park Tameside Drive Castle Bromwich GB Birmingham B 35 7 AG Tel 44 0121 749 2566 Fax 44 0121 749 6217 Internet www rna uk com Email rn...

Отзывы: