AUXILIARY SUPPLY BURDEN
(At 110V DC)
Monitoring mode: Less than 4W
Arc fault detected: Less than 10W for 2s
AUXILIARY SUPPLY
20 - 60V DC
3
6 – 150V DC
OPERATE TIME
Arc fault trip contacts guaranteed to pick up in less than 10ms
including bounce. Typical operate time is 7ms.
CRO trace showing nominal operation time of the trip contacts at
7ms. First contact touch at 6.25ms and fully closed by 7.25ms.
Operation in <10ms is considered acceptable as current check
relay operate time is ~15ms.
ARC SENSOR INPUTS
Two or three independent arc sensor inputs type 1S30 or similar.
Figure 20: 1S30 Arc Fault Sensor (Refer 1S30 Technical Bulletin)
MINIMUM ARC DURATION
The minimum arc “flash” duration required to guarantee operation
of the output contacts is 1.25ms.
TRIP CONTACT RESET TIME
Once operated the trip output contacts reset as per the
configuration switch 4 setting.
MANUAL RESET
Press front button or interrupt power supply to reset LED’s.
Technical Data
OUTPUT CONTACTS
Arc fault trip contacts:
2 N/O
Fail alarm:
1 N/C for the power supply / CPU fail
Normally picked up & drops out to
signal an alarm condition.
OUTPUT CONTACT RATINGS
IEC60255-0-2
Carry continuously
5A AC or DC
0.5s 20A AC or DC
Make & carry
L/R
≤
40ms & V
≤
300V
0.2s 30A AC or DC
AC resistive
AC inductive
1,250VA
250VA @ PF
≤
0.4
DC resistive
75W
Break capacity
I
≤
5A & V
≤
300V
30W @ L/R
≤
40ms
DC inductive
50W @ L/R
≤
10ms
Minimum number of operations
10
6
at maximum load
Minimum recommended load
0.5W limit 10mA / 5V
TRANSIENT OVERVOLTAGE
IEC60255-5
Between all terminals & earth
5kV 1.2/50us 0.5J
Between independent circuits without
amage or flashover
d
5kV 1.2/50us 0.5J
INSULATION COORDINATION
IEC60255-5
Between all terminals & earth
2.0kV RMS for 1 minute
Between independent circuits
2.0kV RMS for 1 minute
Across normally open contacts
1.0kV RMS for 1 minute
AUXILIARY SUPPLY
IEC60255-11
Allowable breaks / dips in supply
Collapse to zero from nominal voltage
≤
20ms
HIGH FREQUENCY DISTURBANCE IEC60255-22-1 CLASS III
2.5kV 1MHz common mode
1
.0kV 1MHz differential mode
No mal operation
ELECTROSTATIC DISCHARGE
IEC60255-22-2 CLASS III
6
kV contact discharge
No mal operation
RADIO FREQUENCY INTERFERENCE
IEC60255-22-3
10V/m, 80 TO 1,000MHz
No mal operation
FAST TRANSIENT
IEC60255-22-4
4kV, 5/50ns, 100KHz repetitive
No mal operation
CONDUCTED RFI
IEC60255-22-6
10V, 0.15 to 80MHz
No mal operation
TEMPERATURE RANGE
IEC68-2-1/2
Operating:
-5 to +55
o
C
Storage:
-25 to +75
o
C
HUMIDITY
IEC68-2-78
40
o
C & 95% RH non condensing
CASE
ZA12 flush or DIN rail mount type
12 M4 screw terminals
Plug in module to facilitate easy wiring & fast changeover
AC AUXILIARY SUPPLIES (PS5R-A24 MODULE)
The Idec PS5R DIN rail mount power supply is suitable for
providing the 24V DC auxiliary supplied required for operating the
S20 Arc Fault Monitor from an AC auxiliary.
1
Vx input:
85 to 264V AC
Power output:
7.5W continuous