OPERATING THE ULTRASONIC COMPUTER
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
Manual USZ 08 · EN05 · 2015-06
23
The DZU operating mode (15) requires another functional unit (remote unit) to be interconnected between
the measuring head and the volume corrector. This is either the external USZ 9000 remote unit which
represents the main totalizer from the point of view of custody transfer metering or the USE 09-C ultrasonic
electronic system with an integrated controller and main totalizer. The DZU protocol transmits meter
readings, flow rates and status information for diagnostic purposes. In the case of the ERZ 2000, a
USZ 9000 is to be connected to the COM 2 interface ("DZU" mode, 9600 baud); a USE 09-C is to be
connected to the COM 1 interface ("DZU" mode, 19200 baud).
Example of the DZU mode (for the USE 09-
C
)
The IGM mode (16) does not require any interconnected hardware (remote unit); the volume
corrector communicates directly with the measuring head of the ultrasonic flowmeter. The
measuring element is to be connected to the COM 1 interface ("USE09" mode, 38400 baud) of the
ERZ 2000.
Example of the IGM mode (for the USE 09)
USE 09-C
USE 09
ERZ 2000
Internal bus
Paths 1, 2
Paths 3, 4
Paths 5, 6
DZU protocol
ERZ 2000
Paths 1, 2
Paths 3, 4
Paths 5, 6
Corrector
Alternatively: pulses
(volume, alarm, direction)