RLE Falcon WiNG-DI
Falcon WiNG-THRM
Falcon WiNG-ANLG Скачать руководство пользователя страница 2

LED

Channel

Selection

Button

3.6V

Lithium

Battery

Antenna

Circuit 

Board

Clip

L Brackets

Plastic Pegs

Antenna Guides

11. If you are installing a WiNG-ANLG sensor:

Connect your analog input to the 

transmitter.  Insert the two stripped wires 

into the 2-pin terminal block connector 

(TB3) - positive wire into the left terminal, 

negative into the right.  Tighten the screws 

on the terminal block connector to secure 

the leads. 
Set the jumpers accordingly.  By default, 

the sensor is configured for a 4-20mA 

analog input - jumpers on pairs 2 and 5.  

If your input is 0-5V, place the jumpers on pairs 1 and 3.  If your input is 

0-10V, place the jumpers on pairs 1 and 4.

Access the individual sensor’s configuration page in the WiNG-MGR UI and 

set the gain and offset for the sensor:

For 4-20mA sensors:

Gain = (Sensor high range value – sensor low range value) ÷ 3085
Offset = Sensor low range – ((Sensor high range value – sensor low 

range value) ÷ 4)  
Example: Temperature sensor with a sensing range of 5-120°F
Gain = (120 - 5) ÷ 3085 = 0.0373
Offset = 5 - ((120-5) ÷ 4) = -23.75

For 0-5V and 0-10V sensors:

Gain = (Sensor high range value – sensor low range value) ÷ 3856
Offset = Sensor low range
Example: Temperature sensor with a sensing range of 5-120°F
Gain = (120 - 5) ÷ 3856 = 0.0298
Offset = 5

10. Check the WiNG-MGR web interface to make sure the sensor status reports 

accurately.

11. Replace the lid, ensuring that the antenna is held in place by the antenna 

guides and feeds out the vent hole in the side of the enclosure. Do not pinch 

the antenna between the lid and the case.

1   2   3   4   5

Jumper pairs:

TB3

Analog

Input

JMP1

Analog Input 

Configuration 

Jumpers -

Set for 4/20mA 

Analog Input

TB1

Digital

Input

TB2

Thermistor

Input