User Guide: LDRA6
Chapter 2: Connections & Settings
5 970
484-6510
www.rletech.com
2-1.1
TB1 – Power
The LDRA6 connects to a 24VDC power supply using TB1, a two position connector labeled 24VDC.
2-1.2
POW1 – Power
Power can also be supplied to the unit through POW1. This is a wall adapter plug connection. This also
requires 24VDC.
2-1.3
TB2, TB3 – Zone Inputs
SeaHawk Leak Detection Cable (SC) and/or dry contact wires connect to the LDRA6 through TB2. Fifteen
foot (4.57m) leader cables (one is included in each leader cable kit, part #LC-KIT) are required for leak
detection cable connections only. Dry contact wires must be user supplied or may be supplied with your
dry contact device. Connect cables/wires as follows:
Position
Leak Detection Cable
Dry Contact Wire
TB3-1
Zone 1 White
Zone 1 Input-1
TB3-2
Zone 1 Black
Zone 1 Input-2
TB3-3
Zone 1 Green
N/A
TB3-4
Zone
1
Red
N/A
TB3-5
Zone 2 White
Zone 2 Input-1
TB3-6
Zone
2
Black
Zone
2
Input-2
TB3-7
Zone 2 Green
N/A
TB3-8
Zone
2
Red
N/A
TB3-9
Zone 3 White
Zone 3 Input-1
TB3-10
Zone
3
Black
Zone
3
Input-2
TB3-11
Zone 3 Green
N/A
TB3-12
Zone
3
Red
N/A
TB2-1
Zone 4 White
Zone 4 Input-1
TB2-2
Zone
4
Black
Zone
4
Input-2
TB2-3
Zone 4 Green
N/A
TB2-4
Zone
4
Red
N/A
TB2-5
Zone 5 White
Zone 5 Input-1
TB2-6
Zone
5
Black
Zone
5
Input-2
TB2-7
Zone 5 Green
N/A
TB2-8
Zone
5
Red
N/A
TB2-9
Zone 6 White
Zone 6 Input-1
TB2-10
Zone
6
Black
Zone
6
Input-2
TB2-11
Zone 6 Green
N/A
TB2-12
Zone
6
Red
N/A
2-1.4
TB5, TB4 – Zone Alarm Relays
These are the Zone Alarm Relay output terminal blocks (Form C). A status LED is located above each
relay, which will indicate the state of the relay (on/off). These relays can be configured as supervised or
unsupervised, latched or unlatched (
unsupervised and unlatched by factory default
). Connect the Zone
Alarm Relay wires to TB3 and TB4 as follows:
TB5-1 Zone 1 alarm relay normally open (NO)
TB5-2 Zone 1 alarm relay common (C)
TB5-3 Zone 1 alarm relay normally closed (NC)
TB5-4 Zone 2 alarm relay normally open (NO)
TB5-5 Zone 2 alarm relay common (C)
TB5-6 Zone 2 alarm relay normally closed (NC)