AirLink 7543 Gas Monitor Operator’s Manual
Chapter 6: Advanced Configuration Menu • 28
•
Channels 1-6 “On”
•
Channel addresses set to 1-6
•
Relays set at “10, 15, 20 and 25”
•
All relays set to “Auto Reset” / “Increasing”
•
Modbus Output Baud set at 9600
•
Radio Timeout set to 10 minutes
•
Network ID set to 5
•
Secondary Monitor
Relay Setup
1. Set Relay 3 as Fault Relay: Press
ADD
or
SUB
(Yes/No—as indicated on the display screen) to
setup Relay 3 as the Fault Relay. To leave the setting as it is, press
MENU
(Next).
NOTE:
With this feature enabled, if any Fault occurs (on any channel) the Fault Relay is engaged. In
addition, Relay 3 is removed from all setup options.
2. Relay 3 as Fault Relay Latching/Auto Reset: Press
ADD
or
SUB
(Yes/No—as indicated on the
display screen) to setup the Relay 3 Fault Relay as latching or auto resetting. To leave the setting
as it is, press
MENU
(Next).
NOTE:
This screen only appears if Relay 3 was set up as the fault relay.
3. Failsafe: Press
ADD
or
SUB
(Yes/No—as indicated on the display screen) to setup Relay 1 as
failsafe (or not failsafe). To leave the setting as it is, press
MENU
(Next).
4. Repeat step 3 for Relays 2 and 3.