65-2496RK/65-2499RK CO Detector • 11

2.

Turn off or unplug power to the controller.

3.

Unscrew the detector housing cap from the detector housing body.

4.

Unplug and remove the old CO sensor with the boot and charcoal filter attached.

5.

Remove the rubber boot and charcoal filter from the old CO sensor.

6.

Remove the replacement CO sensor from its packaging and remove the wire jumper 
that is shorting the WE and RE sensor pins. This wire jumper is installed on the sensor 
pins for shipment or storage but must be removed for the sensor to operate properly 
when installed in a detector.

WARNING: The CO sensor will not operate properly if the wire jumper is not removed.

7.

Install the rubber boot with charcoal filter onto the replacement sensor’s face.

8.

Carefully plug the replacement sensor into the four-socket pattern that is located in 
the detector housing body.

WARNING: You must replace the plug-in sensor with the same type of sensor that is 

installed. A detector cannot be converted from one type of detector to 
another by using a different plug-in sensor. For example, if you are 
replacing an CO sensor, you must replace it with a CO sensor. 

9.

Make sure the cap gasket is in place and screw the detector housing cap back onto the 
detector housing body.

10. Turn on power to the controller.

11. Turn on the controller.

CAUTION: Allow the replacement sensor to warm up for 5 minutes before you continue with the 

next step.

12. Calibrate the detector as described in “Calibration” on page 13.

Replacing the Charcoal Filter

1.

Turn off the controller.

2.

Turn off or unplug power to the controller.

3.

Unscrew the detector housing cap from the detector housing body.

4.

Unplug and remove the CO sensor with the boot and charcoal filter attached.

5.

Remove the rubber boot that secures the charcoal filter to the CO sensor.

6.

Remove the charcoal filter from the rubber boot.

7.

Place the replacement filter in the rubber boot in the same position as the filter you 
removed in the previous step.

8.

Reinstall the rubber boot with charcoal filter on the CO sensor.

9.

Carefully plug the replacement sensor into the socket pattern that is located in the 
detector housing body.

10. Make sure the cap gasket is in place and screw the detector housing cap back onto the 

detector housing body.

11. Turn on power to the controller.

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание 65-2496RK

Страница 1: ...65 2496RK 65 2499RK Carbon Monoxide Detector Operator s Manual Part Number 71 0156RK Revision 0 Released 2 16 11 www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Страница 2: ...or is essential for proper operation and correct readings Please calibrate and maintain this detector regularly Frequency of calibration depends upon the type of use you have and the sensor types Typi...

Страница 3: ...on costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS EXPRESSED OR IMPLIED AND ALL OTHER OBLIGATION...

Страница 4: ...ing Incoming Power 7 Setting the Zero Fresh Air Reading 7 Maintenance 8 Preventive Maintenance 8 Troubleshooting 9 Replacing Components of the CO Detector 10 Calibration Frequency 13 Calibration 13 Pr...

Страница 5: ...x and junction box terminal strip Specifications WARNING Do not use this product in a manner not specified in this instruction manual Table 1 lists specifications for the 65 2496RK and 65 2499RK CO de...

Страница 6: ...omponent Location 65 2496RK CO Detector The 65 2496RK CO detector consists of the detector housing body detector housing cap cap gasket plug in sensor and the charcoal filter with rubber boot Figure 2...

Страница 7: ...ls the interface between the housing and cap Plug In Sensor The plug in sensor is secured in the detector assembly by the housing cap Through a series of chemical and electrical reactions the sensor p...

Страница 8: ...ng site Select a site where the detector is not likely to be bumped or disturbed Make sure there is sufficient room to perform start up maintenance and calibration procedures Select a site where the t...

Страница 9: ...d construction technique for the environmental rating of the junction box The junction box is rated NEMA 4X 6 Connect the two wires to the detector using the terminal block CAUTION If using shielded c...

Страница 10: ...o an available chassis ground at the controller RKI controllers typically have a ground stud that is a convenient grounding location Red Shielded Cable S Controller Detector Terminals Typical Designat...

Страница 11: ...Zero Fresh Air Reading CAUTION If you suspect the presence of CO in the monitoring environment use the calibration kit and a zero air calibration cylinder to introduce fresh air to the CO detector and...

Страница 12: ...external alarms before performing this test Preparing for the response test 1 Place the controller into its calibration program or disable external alarms 2 Verify that the controller display reading...

Страница 13: ...ctor housing body The detector s zero reading is low enough to cause a fail condition The detector is malfunctioning Recommended action Verify that the detector wiring is correct and secure Confirm th...

Страница 14: ...uments Inc for further instruction Unexplained Gas Readings Symptom The display indicates a CO reading when CO is known not to be present Probable causes The detector needs calibration The charcoal fi...

Страница 15: ...g an CO sensor you must replace it with a CO sensor 9 Make sure the cap gasket is in place and screw the detector housing cap back onto the detector housing body 10 Turn on power to the controller 11...

Страница 16: ...er Note the position of the color coded leads as you remove them If the detector is installed remotely from a controller in a junction box disconnect the detector leads from the terminal block in the...

Страница 17: ...every 3 months may be necessary Calibration This section describes how to calibrate the CO detector It includes procedures to prepare for calibration set the fresh air reading set the response readin...

Страница 18: ...the directions in the controller operator s manual for setting the response span reading 3 When the instructions call for exposing the detector to gas turn the regulator s on off knob counterclockwis...

Страница 19: ...r s Manual this document 81 0064RK Calibration cylinder 50 PPM CO in air 17 liter steel 81 0064RK 01 Calibration cylinder 50 PPM CO in air 34 liter steel 81 0064RK 03 Calibration cylinder 50 PPM CO in...

Отзывы: