background image

 

65-2435RK CO Transmitter • 7

Test Points

The test points (labeled 

TP-

 and 

TP+

) are near the top of the amplifier. The test points 

produce a 100 to 500 mV output that is proportional to the transmitter’s 4 to 20 mA output. 
Use the test points and a voltmeter to measure the transmitter’s output during the start-up and 
calibration procedures.

Junction Box

Use the junction box to install the CO transmitter at a mounting site that is remote from the 
controller. The junction box also protects the amplifier and wiring connections made to the 
amplifier. Use the two 3/4 NPT conduit hubs to mount the detector to the junction box (bottom 
hub) and connect wiring from the amplifier to the controller (top hub).

NOTE:

The CO detector and amplifier are factory-mounted to the junction box.

Use the junction box’s two mounting holes to mount the CO transmitter to a vertical surface at 
the monitoring site. Use the cover on the front of the junction box to access the interior of the 
junction box.

Installation

This section describes procedures to mount the CO transmitter in the monitoring environment 
and wire the transmitter to a controller.

Mounting the CO Transmitter

1. Select a mounting site that is representative of the monitoring environment. Consider the 

following when you select the mounting site.

Select a site where the transmitter is not likely to be bumped or disturbed. Make sure 
there is sufficient room to perform start-up, maintenance, and calibration procedures.

Select a site where the target gas is likely to be found first.

NOTE:

If your application does not require a specific mounting site, mount the transmitter at 
approximately breathing level.

Содержание 65-2435RK

Страница 1: ...RKI Instruments Inc www rkiinstruments com 65 2435RK Hydrogen Compensated Carbon Monoxide Transmitter Operator s Manual Part Number 71 0073RK Revision B Released 7 6 20...

Страница 2: ...t costs local repair costs transportation costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS EXPRES...

Страница 3: ...oller 8 Startup 10 Introducing Incoming Power 10 Setting the Zero Signal 10 Operating With a Background of Hydrogen 10 Maintenance 11 Preventive Maintenance 11 Troubleshooting 12 Replacing Components...

Страница 4: ...he end of this manual lists replacement parts and accessories for the CO transmitter Specifications Table 1 lists specifications for the CO transmitter Table 1 Specifications Target Gas Carbon Monoxid...

Страница 5: ...ludes a flame arrestor which contains any sparks which may occur within the detector housing Two cap gaskets seal the interface between the housing and cap Two wires extend from the top of the detecto...

Страница 6: ...t the CO detector to the amplifier and the amplifier to a controller The terminal strip is a plug in style which can be removed for wiring by pulling up on it NOTE The CO detector is factory wired to...

Страница 7: ...mplifier are factory mounted to the junction box Use the junction box s two mounting holes to mount the CO transmitter to a vertical surface at the monitoring site Use the cover on the front of the ju...

Страница 8: ...rews through the junction box s two mounting holes to secure the junction box to a vertical surface CAUTION Mount the CO transmitter with the detector facing down see Figure 2 Wiring the CO Transmitte...

Страница 9: ...ical code when installing the conduit seal 6 Connect the two wires to the terminal strip as follows see Figure 3 Connect the positive wire to the terminal labeled 24V Connect the feedback wire to the...

Страница 10: ...iring the CO Transmitter to a Controller 10 Connect the cable s drain to an available chassis ground at the controller FB CO Detector H2 Compensated Factory Wired 24 VDC 19 30 VDC TP TP 4 20mA Transmi...

Страница 11: ...he sensor and verify an accurate zero setting 1 Verify that the transmitter is in a fresh air environment environment known to be free of carbon monoxide other toxic and combustible gases and of norma...

Страница 12: ...roblems you may encounter with the CO transmitter NOTE This troubleshooting guide describes transmitter problems only See the controller instruction manual for problems you may encounter with the cont...

Страница 13: ...fier A procedure to replace the entire detector assembly is at the end of this section In most cases it is not necessary to replace the entire detector assembly Replacing the Sensor 4 Turn off the con...

Страница 14: ...ation may not work properly 16 Calibrate the replacement sensor as described in the Calibration section of this manual Replacing the Charcoal Filter 1 Turn off the controller 2 Turn off or unplug inco...

Страница 15: ...d amplifier 8 Use the two screws you removed in step 5 to secure the new amplifier to the junction box 9 Reconnect the wiring from the controller to the interconnect terminal strip as shown in Table 2...

Страница 16: ...detector leads of the replacement detector through the bottom conduit hub of the junction box then screw the mounting threads of the detector into the conduit hub 7 Connect the detector leads to the...

Страница 17: ...ttom of the CO detector 2 Use the sample tubing to connect the fixed flow regulator to the calibration cup NOTE Do not screw the regulator into the hydrogen cylinder at this time 3 Set a voltmeter to...

Страница 18: ...onents of the calibration kit connected by the sample tubing 3 Secure the junction box cover to the junction box 4 Return the controller to normal operation 5 Verify that the controller display readin...

Страница 19: ...re continuing Setting the Zero Reading NOTE If you can verify that the CO transmitter is in a fresh air environment you do not need to apply zero air to the detector before adjusting the zero reading...

Страница 20: ...e leave the components of the calibration kit connected by the sample tubing 3 Secure the junction box cover to the junction box 4 When the display reading falls below the alarm setpoints return the c...

Страница 21: ...get gas when ordering 65 2009RK CO replacement sensor 65 2435RK CO transmitter includes detector and amplifier 65 2470RK CO replacement detector assembly includes sensor 71 0073RK 65 2435RK Hydrogen C...

Отзывы: